Binary control
Operating Instructions – MOVIMOT
®
flexible
173
7.2.4
Configuration 3: Enable, external fault, setpoint changeover
Fixed setpoint processing mode:
Mechanical setting elements
(cannot be changed)
Behavior of the drive unit
Digital input
"DRIVE"
LED
DI01
DI02
DI03
DI04
Enable
Ex-
ternal
fault
Poten-
tiometer
f2
Reset
The drive unit stops with deceleration setpoint t1.
1)
FCB 01 Output stage inhibit is activated afterwards.
0
1
x
x
Lights up
yellow
The drive unit is running in positive direction of rotation
(clockwise rotation) with speed setpoint f1.
2)
The acceleration setpoint t1 is active.
1)
1
1
0
x
Illuminated
in green
The drive unit is running in positive direction of rotation
(clockwise rotation) with speed setpoint f2.
The acceleration setpoint t1 is active.
1)
1
1
1
x
Illuminated
in green
The drive unit is in state "External terminal fault".
1
0
x
x
Flashing
red
The fault state has been reset.
0
1
0
1
Lights up
yellow
1) If potentiometer t1 is deactivated using the parameter settings, the acceleration setpoint 1/ deceleration setpoint 1 of the fixed set-
point processing will be activated.
2) If DIP switch S2/2 (Analog setpoint selection) is set to "ON", the speed setpoint of analog input AI1 is used instead of speed setpoint
f1.
0 = No voltage
1 = 24 V
x = Any