7
Operation
Binary control
Operating Instructions – MOVIMOT
®
flexible
172
7.2.3
Configuration 2: Enable, fixed setpoints
Fixed setpoint processing mode:
Mechanical setting elements
(cannot be changed)
Behavior of the drive unit
Digital input
"DRIVE"
LED
DI01
DI02
DI03
DI04
Enable
Fixed
setpoint
2
0
Fixed
setpoint
2
1
Reset
The drive unit stops with deceleration setpoint t1.
1)
FCB 01 Output stage inhibit is activated afterwards.
0
x
x
x
Lights up
yellow
The drive unit is running with the fixed speed setpoint 1.
The direction of rotation is specified by the sign of the
fixed setpoint.
The acceleration setpoint t1 is active.
1)
1
1
0
x
Illuminated
in green
The drive unit is running with the fixed speed setpoint 2.
The direction of rotation is specified by the sign of the
fixed setpoint.
The acceleration setpoint t1 is active.
1)
1
0
1
x
Illuminated
in green
The drive unit is running with the fixed speed setpoint 3.
The direction of rotation is specified by the sign of the
fixed setpoint.
The acceleration setpoint t1 is active.
1)
1
1
1
x
Illuminated
in green
The drive unit is running in positive direction of rotation
(clockwise rotation) with the analog speed setpoint f1.
2)
The acceleration setpoint t1 is active.
1)
1
0
0
x
Illuminated
in green
The drive unit is in fault state.
x
x
x
x
Lights up
or flashes
red
The fault state has been reset.
0
0
0
1
Lights up
yellow
1) If potentiometer t1 is deactivated using the parameter settings, the acceleration setpoint 1/ deceleration setpoint 1 of the fixed set-
point processing will be activated.
2) If DIP switch S2/2 (Analog setpoint selection) is set to "ON", the speed setpoint of analog input AI1 is used instead of speed setpoint
f1.
0 = No voltage
1 = 24 V
x = Any
29129451/EN – 12/2019