7
Operation
Binary control
Operating Instructions – MOVIMOT
®
flexible
175
7.2.6
Configuration 5: Motor potentiometer CCW
Fixed setpoint processing mode:
Motor potentiometer
(cannot be changed)
Behavior of the drive unit
Digital input
"DRIVE"
LED
DI01
DI02
DI03
DI04
Left
Motor
poten-
tiomete
r up
Motor
poten-
tiometer
down
Reset
The drive unit stops with deceleration setpoint t1.
1)
FCB 01 Output stage inhibit is activated afterwards.
0
x
x
x
Lights up
yellow
The drive unit is running in negative direction of rotation
(counterclockwise rotation) with the speed setpoint "Mo-
tor potentiometer".
The acceleration setpoint t1 is active.
1)
1
0
0
x
Illuminated
in green
The drive unit is running in negative direction of rotation
(counterclockwise rotation) with the
increasing
speed
setpoint "Motor potentiometer".
2)
The change in speed is defined by the parameter
Accel-
eration
of the motor potentiometer function.
1
1
0
x
Illuminated
in green
The drive unit is running in negative direction of rotation
(counterclockwise rotation) with the
decreasing
speed
setpoint "Motor potentiometer".
2)
The change in speed is defined by the parameter
Decel-
eration
of the motor potentiometer function.
1
0
1
x
Illuminated
in green
The drive unit is running in negative direction of rotation
(counterclockwise rotation) with the
constant
speed
setpoint "Motor potentiometer".
1)
The acceleration setpoint t1 is active.
1)
1
1
1
x
Illuminated
in green
The drive unit is in fault state.
x
x
x
x
Lights up
or flashes
red
The fault state has been reset.
0
0
0
1
Lights up
yellow
1) If potentiometer t1 is deactivated using the parameter settings, the acceleration setpoint 1/ deceleration setpoint 1 of the fixed set-
point processing will be activated.
2) The speed setpoint of the motor potentiometer can only be changed when the drive unit is enabled.
0 = No voltage
1 = 24 V
x = Any
29129451/EN – 12/2019