Operation
DynaStop® in conjunction with STO
Operating Instructions – MOVIMOT
®
flexible
187
7.7.2
Drive behavior when STO is activated before rotational speed "0" is reached
NOTICE
Danger due to incorrect parameter settings
If the parameter
Apply brake/activate DynaStop
®
in STO state
is set to
"1"
, (path:
Functions
>
Drive functions
>
FCB 01 Output stage inhibit
>
Brake/DynaStop
®
), the
DynaStop
®
function can be activated outside of the permitted operating range. This
can cause high torque loads / high motor currents, which may damage the drive unit
and the application.
Possible damage to property.
•
Use the factory settings or recommended settings.
If STO is activated before the motor has come to standstill (rotational speed = 0), the
DynaStop
®
function behaves as set in parameter
Apply brake/DynaStop
®
in STO state
(Path:
Functions
>
Drive functions
> FCB 01
Output stage inhibit
>
Brake/DynaStop
®
):
Index
Parameter
Setting
Meaning
8501.3
Apply brake/activate
DynaStop
®
in STO
state
(Path:
Functions >
Drive functions >
FCB 01 Output
stage inhibit >
Brake/DynaStop
®
)
0 (no)
The DynaStop
®
status remains unchanged when
STO is activated.
•
Depending on the application, the motor coasts
to a halt or even accelerates.
•
The stopping distance is not defined.
1 (yes)
DynaStop
®
is activated (not safety-related) when
STO is enabled.
•
In case DynaStop
®
is activated before the rota-
tional speed has reached "0", high torques/motor
currents can occur that may damage the drive
and the application.
•
Evaluate the possible consequences.
•
The stopping distance is not defined.
Recommended setting/factory setting