10
Project planning
Selecting an inverter
Operating Instructions – MOVIMOT
®
flexible
294
10.7.1
Overload capacity
Load cycle with base load current – typical for the selection of asynchronous and servomotors
The characteristic load cycle consists of a load and a load relief period. In the load re-
lief period, the output current must not exceed the specified value. After this load relief
period, overload is possible again.
t
t
1
t
2
I
I
out1
I
out2
18014415982173963
Overload capacity at f
PWM
= 4 kHz, f
A
≥ 3 Hz
Overload current I
out 1
/I
N
Overload time t
1
Base load current I
out 2
/I
N
Required pause interval t
2
200%
3 s
50%
7 s
200%
3 s
100%
17 s
150%
60 s
100%
60 s
150%
60 s
50%
30 s
29129451/EN – 12/2019