Operations Switched PDU
Installation and Operations Manual
Changing the UPS type:
The Set UPS Type command is used to change the type of UPS for each UPS record.
To change a UPS record:
At the Switched CDU: prompt, type
set ups type
and press
Enter
.
At the prompt, type the index number for the UPS record to be changed and press
Enter
.
At the prompt, type the corresponding number from the list of the UPS types and press
Enter
.
Example
The following command changes UPS type for the record at index number 2 to ‘MGE’:
Switched CDU: set ups type<Enter>
1 Type: Liebert
Host/IP: DC1Liebert1
2 Type: Powerware
Host/IP: DC1Powerware1
Select UPS(1-8): 2<Enter>
UPS types:
1 -- APC
2 -- Liebert
3 -- MGE
4 -- Tripp Lite
5 -- Generic (RFC1628)
6 -- Hewlett Packard
7 -- Minuteman
8 -- Mitsubishi
9 -- Powerware
10 -- Toshiba
11 -- Falcon Electric
Select type(1-11): 3<Enter>
Changing the UPS host address:
The Set UPS Host command is used to change the IP address or hostname for each UPS record. Hostnames can be up
to 60 characters long.
To change a UPS host address:
At the Switched CDU: prompt, type
set ups host
and press
Enter
.
At the prompt, type the index number for the UPS record to be changed and press
Enter
.
At the prompt, type IP address or hostname for the UPS and press
Enter
.
Example
The following command changes UPS hostname for the record at index number 2 to ‘DC1MGE1’:
Switched CDU: set ups host<Enter>
1 Type: Liebert
Host/IP: DC1Liebert1
2 Type: MGE
Host/IP: DC1Powerware1
Select UPS(1-8): 2<Enter>
Host/IP: DC1MGE1<Enter>