Switched PDU
Installation and Operations Manual
Advanced Operations
133
Setting the RADIUS server address:
The Set RADIUS Server command sets the IP address or hostname of the primary or secondary server used for
RADIUS authentication requests.
NOTE:
Both IPv4 and IPv6 formats are accepted for primary/secondary IP address or hostname.
To set the RADIUS server address:
At the Switched CDU: prompt, type
set radius
, followed by
primary
or
secondary
, followed by
server
, and the
RADIUS server’s IP address or hostname (maximum 63 characters). Press
Enter
.
Examples
The following command sets the primary RADIUS server address to 98.76.54.32:
Switched CDU: set radius primary server 98.76.54.32<Enter>
The following command sets the secondary RADIUS server address to radius.servertech.com:
Switched CDU: set radius secondary server radius.servertech.com<Enter>
Setting the RADIUS secret:
The Set RADIUS Secret command sets the shared secret for the server used for RADIUS authentication requests.
To set the shared secret:
At the Switched CDU: prompt, type
set radius
, followed by
primary
or
secondary
, and followed by
secret
. Press
Enter
.
Enter the shared secret and press
Enter
. For security, shared secret characters are not displayed.
The secret that was set for the primary server will not be cleared when setting the secret for the secondary server, and
vice versa.
Changing the RADIUS port number:
The Set RADIUS Port command sets the server port number for RADIUS authentication requests.
To change the port number:
At the Switched CDU: prompt, type
set radius
, followed by
primary
or
secondary
, followed by
port
, and the port
number (1-65535). Press
Enter
.
The default is 1812.
Example
The following command sets the secondary RADIUS server port number to 1855:
Switched CDU: set radius secondary port 1855<Enter>
Setting the RADIUS timeout value:
The Set RADIUS Timeout command sets the time interval to wait for a reply from the RADIUS server before
resending the authentication request.
To set the timeout value:
At the Switched CDU: prompt, type
set radius
, followed by
primary
or
secondary
, followed by
timeout
, and the
time interval in seconds (1-30). Press
Enter
.
Examples
The following command sets the primary RADIUS server timeout value to 15 seconds:
Switched CDU: set radius primary timeout 15<Enter>
The following command sets the secondary RADIUS server timeout value to 5 seconds:
Switched CDU: set radius secondary timeout 5<Enter>