Switched PDU
Installation and Operations Manual
Advanced Operations
115
Displaying trap configuration Information:
The Show Traps command displays information about all traps.
To display trap information:
At the Switched CDU: prompt, type
show traps
and press
Enter
.
Example
The following command requests trap configuration information:
Switched CDU: show traps <Enter>
Tower trap configuration:
Tower Tower Status
ID Name Trap
.A Florida_HQ_1 ON
.B Florida_HQ_2 ON
More (Y/es N/o): y
Input feed trap configuration:
Input Input Status Load High
Feed ID Feed Name Trap Trap Load
.AA HQ_1_Infeed_A ON ON 255 A
.BA HQ_2_Infeed_A ON ON 255 A
More (Y/es N/o): y
Outlet trap configuration:
Outlet Outlet Stats Change
ID Name Trap Trap
.AA1 DataServer_1 ON OFF
.AA2 WebServer_1 ON OFF
.AA3 FileServer_1 ON OFF
.AA4 ON OFF
.AA5 ON OFF
.AA6 ON OFF
.AA7 ON OFF
.AA8 ON OFF
.AB1 ON OFF
.AB2 ON OFF
.AB3 ON OFF
.AB4 ON OFF
.AB5 ON OFF
.AB6 ON OFF
.AB7 ON OFF
.AB8 ON OFF
More (Y/es N/o): y
Environmental Monitor .A trap configuration:
Name: Florida_HQ_1
Status Trap: ON
Temperature/Humidity Sensor .A1 Temperature/Humidity Sensor .A2
Name: Temp_Humid_Sensor_A1 Name: T/H2_Florida_HQ_1
Status Trap: ON Status Trap: ON
Temp Trap: ON Temp Trap: ON
Low: 31 Deg.F Low: 32 Deg.F
High: 253 Deg.F High: 253 Deg.F
Delta: 5 Deg.F Delta: 2 Deg.F
Humid Trap: ON Humid Trap: ON
Low: 5 % RH Low: 0 % RH
High: 100 % RH High: 100 % RH
Delta: 2 % RH Delta: 2 % RH