Environmental Monitoring
Sensors
The Sensors page displays:
Absolute and descriptive names of the temperature/humidity sensor
Temperature/humidity sensor readings and percentage of relative humidity
Monitor pages (like the Sensors page) refresh occasionally to reflect current PDU status.
Temperature/Humidity Sensor Status
Status
Description
Found
The PDU found the sensor and connection is established.
Not Found
On a fresh reboot, the PDU does not find a sensor.
Lost
The connection to a previously found sensor is now lost.
No Comm
Communication loss occurred due to a hardware issue (not loss of communication with the probes).
1
1
= The ENV part of the sensor supports two Temperature/Humidity (T/H) probes as part of the master unit, two T/H
probes as part of the link unit, and the optional EMCU-1-1 (which can support two T/H probes, four contact-closure
monitoring points, and one water sensor). The “No Comm” sensor status is not loss of communication with probes
themselves.
Shutdown
The Shutdown section offers access to all Remote Shutdown configuration options. This section is available to
administrative level users only. For more information and the configuration requirements, see the “Remote
Shutdown” section.
Outlets
Enabling or disabling Remote Shutdown support:
Select or deselect outlets to enable/disable Remote Shutdown support for in the Shutdown/Delay field and click
Apply
.
Setting the Remote Shutdown delay:
Enter the shutdown delay (in seconds) in the outlet Shutdown/Delay field and click
Apply
. Valid range is 1-900
seconds.
Editing the target server’s Hostname/IP address:
In the outlet Hostname/IP field, enter an IP address or Hostname and click
Apply
.
Enabling or disabling shutdown script support:
Select or deselect outlet to enable/disable shutdown script support for in the Script/Delay column and click
Apply
.
Setting the shutdown script delay:
Enter the shutdown delay (in minutes) in the outlet Script/Delay field and click
Apply
.
Configuration
The Configuration section offers access to all unit configuration options. This section is available to administrative
level users only.
System
The System configuration page is used for reference of system information such as Ethernet NIC Serial Number,
Ethernet MAC address and system firmware and hardware revisions as well as assignment and maintenance of other
system wide configurations.
For descriptive names, up to 24 alphanumeric and other typed characters (ASCII 33-126 decimal) are allowed; spaces
are not allowed.
NOTE:
Spaces can be used for the location description only.