126

 

 Advanced Operations   

     Switched PDU 

  

 

Installation and Operations Manual 

 

The Switched PDU family of products supports the Terminal Access Controller Access Control System () 
protocol.  This enables authentication and authorization with a central  server; user accounts do not need to 
be individually created locally on each PDU.   

This allows administrators to pre-define and configure (in each product, and in the  server) a set of 
necessary  privilege levels, and users access rights for each.  User’s access rights can then be assigned or 
revoked simply by making the user a member of one-or-more pre-defined  privilege levels.  User account 
rights can be added, deleted, or changed within   without any changes needed on individual products. 

The PDU supports 16 different  privilege levels; 15 are entirely configurable by the system administrator 
(1 is reserved for default Admin level access to all PDU resources). 

TACAC+ Command Summary 

Command 

Description 

Set Authorder 

Specifies the authentication order for each new session attempt 

Set TACACS 

Enables/disables TACACS support  

Set TACACS Host 

Sets the IP address or hostname of the TACACS server 

Set TACACS Key 

Sets the TACACS encryption key 

Set TACACS Port 

Sets the TACACS server port number 

Show TACACS 

Displays TACACS configurations 

Add GrouptoTACACS 

Grants a TACACS account access to one or more groups 

Add OutlettoTACACS 

Grants a TACACS account access to one or more outlets 

Add PorttoTACACS 

Grants a TACACS account access to one or more serial ports 

Delete GroupfromTACACS 

Removes access to one or more groups for a TACACS account  

Delete OutlettoTACACS  

Removes access to one or more outlets for a TACACS account 

Delete PortfromTACACS 

Removes access to one or more serial ports for a TACACS account 

Set TacPriv Access 

Sets the access level for a TACACS account 

Set TacPriv Envmon 

Grants or removes user access to environmental monitoring 

List TacPrivs  

Displays access levels for all TACACS accounts 

List TacPriv  

Displays all accessible outlet/groups/ports for a TACACS account 

Enabling and setting up  support 

There are a few configuration requirements for properly enabling and setting up  support.  Below is an 
overview of the minimum requirements: 

1.

 

Enable  support. 

2.

 

Define the IP address and domain component of at least one server. 

3.

 

Set the  key configured on the supporting server. 

Enabling and disabling  support: 

The Set TACACS command is used to enable or disable  support. 

To enable or disable   support: 

At the Switched CDU: prompt, type 

set tacacs

, followed by 

enabled 

or 

disabled

 and press 

Enter

Содержание Switched Rack PDU

Страница 1: ...Switched Rack Power Distribution Unit Installation and Operations Manual Firmware Version 7 0 ...

Страница 2: ...040 Sandhill Drive Reno Nevada 89521 USA All Rights Reserved This publication is protected by copyright and all rights are reserved No part of it may be reproduced or transmitted by any means or in any form without prior consent in writing from Server Technology The information in this document has been carefully checked and is believed to be accurate However changes are made periodically These ch...

Страница 3: ...ety Earth Ground Connection 14 Mounting the PDU 15 Attaching the Expansion Module 16 Connecting to the Power Source 16 Connecting Devices 16 Connecting the Sensors 16 Connecting to the Unit 16 CHAPTER 3 OPERATIONS 19 Interfaces 21 Web Interface 22 Command Line Interface 53 CHAPTER 4 ADVANCED OPERATIONS 97 SSL 98 SSH 100 SNMP Thresholds 102 LDAP 116 TACACS 126 RADIUS 132 Logging 136 Upload Download...

Страница 4: ...Configure location and Switched PDU names Configure sensor names Configure new user account s Remove the predefined Administrator account admn 7 Connect the Switched PDU to the network Technical Support Experience Server Technology s FREE Technical Support Server Technology understands that there are often questions when installing and or using a new product Free Technical Support is provided from...

Страница 5: ...Power Pivot capability can deliver a solution for several types of PDU installations and mountings setting the correct cord angle for overhead power offset overhead power concrete floor raised floor and intra rack power PDU Power Pivot Flexible Cord Design To learn more about PDU Power Pivot and watch a brief video that animates the PDU Power Pivot mounting angles in the equipment rack see the Ser...

Страница 6: ...t LED s displays the current load for each infeed branch or electrical phase per infeed 3 Two RJ45 connectors for Serial RS 232 and Ethernet connection 4 Two mini RJ11 connectors for Temperature Humidity sensors A number is printed above each outlet These numbers can be used in commands that require an outlet name 1 2 4 3 4 3 2 1 Switched Rack Power Distribution Unit ...

Страница 7: ...address used for client based configurations This address is always present in the Server Technology dual stack and cannot be disabled DHCPv6 Stateless Auto Configured Address RFC 3736 A stateless Dynamic Host Configuration Protocol DHCP service for IPv6 DHCPv6 This address is used by nodes to obtain configuration information such as addresses of DNS recursive name servers that do not require the ...

Страница 8: ...wait to acquire an address based on DHCP configuration settings This setting is the default Dual IPv6 IPv4 DHCP disabled static IPv6 IPv4 If the IPv6 Static Address and prefix of the PDU are valid they will be set Otherwise the PDU will attempt to use DHCPv6 to obtain an IPv6 address In addition if the IPv4 Static Address and Net Mask of the PDU are valid they will be set Dual IPv6 IPv4 DHCP enabl...

Страница 9: ...1 DNS1 10 1 5 133 DNS2 10 1 5 134 DHCP Settings DHCP Enabled FQDN Enabled sentry3 524104 Boot Delay Enabled Static Fallback Enabled Network Services Telnet Enabled Port 23 SSH Enabled Port 22 Auth Password Kb Int HTTP Enabled Port 80 SSL Enabled Port 443 Installed Cert User Encrypted Access Optional Stored Files Cert Key User Cert Enabled User Passphrase set SNMPv1 2 Enabled Port 161 TrapPort 162 ...

Страница 10: ...Models with C20 Inlets Separate power input Optional power input retention bracket hardware can be installed two removable T brackets with two 40 mm screws per input Note This bracket is not compatible with Server Technology Input Power Cords with the self locking C19 feature These power cords have the prefix PTCORD L Optional Accessories Temperature humidity sensors Part Number EMTH 1 1 Environme...

Страница 11: ...d muss alle relevanten Codes und Bestimmungen erfüllen Für Installation in Nordamerika müssen Ausschalter bzw Sicherung über 10 000 A Unterbrechungskapazität verfügen Models with unterminated power cords Input connector must be installed by qualified service personnel Input connector rating must meet all applicable codes and regulations Modèles avec cordons d alimentation non terminées Le connecte...

Страница 12: ... equipment or subassembly is suitable for connection to intra building or unexposed wiring or cabling only The intra building port s of the equipment or subassembly MUST NOT be metallically connected to interfaces that connect to the OSP or its wiring These interfaces are designed for use as intra building interfaces only Type 2 or Type 4 ports as described in GR 1089 CORE Issue 5 and require isol...

Страница 13: ...ching the bracket to the IEC 60320 C20 inlet to the enclosure b Remove the Retention Bracket Assembly c Re attach the two screws to the IEC C20 and securely tighten 2 Push the C19 from the Detachable Input Cord firmly into the C20 inlet to ensure it is properly seated C20 Inlet without Retention Bracket Assembly KIT 0016 Retention Bracket Assembly Procedure B If the unit was supplied with a Detach...

Страница 14: ...y Most PDUs will have it located near the power cord entry located near the symbol User supplied materials One 5 mm internal or external tooth star washer One 4 0 mm2 10 AWG wire with 5 mm ring terminal One metric M5 x 6 mm coarse pitch screw Instructions 1 Connect one end of the ground wire to the equipment cabinet or local ground 2 Locate the PDU external ground near the symbol 3 Connect the oth...

Страница 15: ...e slots allow about 6 mm 0 25 inch of horizontal adaptability to align with the mounting holes of your rack Vertical The Switched PDU is supplied with button mounting kit s Distribute the buttons vertically and attach to the PDU as appropriate for the cabinet An additional 19 mm 0 75 inch of clearance is required at the top of the PDU to allow the button to mount into the keyholes Note For more in...

Страница 16: ...the off position until after it is plugged into the outlet 2 Connect devices to the PDU outlets NOTE Server Technology recommends even distribution of attached devices across all available outlets to avoid exceeding the outlet branch or phase limitations Always disconnect ALL power supply cords before opening to avoid electrical shock Afin d éviter les chocs électriques débranchez TOUTES les cable...

Страница 17: ...on out of the box through either Telnet or Web NOTE When installed on a DHCP enabled networks the following network defaults do not apply because the PDU ships with DHCP support enabled IP address 192 168 1 254 Subnet Mask 255 255 255 0 Gateway 192 168 1 1 The local PC network connection must be configured as noted below NOTE For instructions about reconfiguring the network connection contact your...

Страница 18: ......

Страница 19: ...SH 33 HTTP SSL 34 Serial Ports 35 Towers 37 Input Feeds 38 UPS 38 Outlets 39 Groups 39 Users 40 FTP 42 SNTP Syslog 43 SNMP Thresholds 44 LDAP 46 TACACS 48 RADIUS 50 SMTP Email 51 Features 52 Tools 52 Ping 52 Change Password 52 Firmware 52 View Log 52 Restart 52 COMMAND LINE INTERFACE 53 Logging In 53 Operations Commands 56 Administration Commands 61 User Administration 61 Outlet Administration 65 ...

Страница 20: ...ons Switched PDU Installation and Operations Manual Sentry Power Manager SPM Administration 86 Telnet Administration 87 FTP Administration 87 SNTP Administration 89 UPS Administration 91 Feature Administration 95 ...

Страница 21: ...outlet 8 on the B infeed of tower A is AB8 Outlets can also be included in one or more named groups of outlets enabling you to issue a command that affects all outlets in a named group Usernames and Passwords The Switched Cabinet Distribution Unit has one predefined administrative user account username password admn admn and supports a maximum of 112 defined user accounts NOTE For security Server ...

Страница 22: ... PDU location string IP address in the System Header section may not work with all web browsers This example shows the Outlet Control Individual page Example of Firmware Web Interface for the Switched PDU Logging In Logging in through the Web interface requires directing the Web client to the configured IP address of the unit To log in by Web interface In the login window enter a valid username an...

Страница 23: ...monitoring new installation or power distribution changes in high density computing environments Power system administrators can also quickly identify thermal and humidity concerns that might otherwise escalate into costly infrastructure repairs if left unchecked As long as the System Summary page is active the sensor graphs are continually updating system statistics and threshold values The data ...

Страница 24: ...nvironmental monitor NOTE The temperature threshold values are user defined You must configure these threshold values on the SNMP Thresholds page or the Command Line Interface CLI Humidity Status The Humidity Status graph displays a blinking error whenever humidity exceeds the low or high threshold The PDU will continue to display this state until the condition changes or the problem has been reso...

Страница 25: ...ion was lost to a sensor that was previously detected and the sensor is pulled from the original environment monitoring statistics There is no data to report the graph is meaningless and the threshold settings remain displayed but are grayed Sensor Graph Color Coding The following colors change dynamically on the sensor graphs to communicate operating conditions Line Load Status Green Normal Yello...

Страница 26: ... PDU and the outlet load in amperes Available outlet and group power states can be set to on off or reboot Individual The Individual outlet control page displays all outlets assigned to the current user The user can apply on off or reboot actions to individual multiple or all accessible outlets To apply actions to individual or multiple outlets In the Individual Outlet Control section select the d...

Страница 27: ...o Comm varies Communication to the outlet has been lost Control state will be applied when communication is re established Power Monitoring Input Feeds The Input Feeds page displays The absolute and descriptive names of the infeed Infeed status Input branch phase load in amperes Input Voltage Calculated power usage in Watts Monitor pages like the Input Feeds page refresh occasionally to reflect cu...

Страница 28: ...mation and the configuration requirements see the Remote Shutdown section Outlets Enabling or disabling Remote Shutdown support Select or deselect outlets to enable disable Remote Shutdown support for in the Shutdown Delay field and click Apply Setting the Remote Shutdown delay Enter the shutdown delay in seconds in the outlet Shutdown Delay field and click Apply Valid range is 1 900 seconds Editi...

Страница 29: ...tion From the Display Orientation drop down list select Normal or Inverted and click Apply NOTES Only specific PDU models are equipped with an accelerometer chip that senses device orientation If equipped your PDU automatically aligns the LED display orientation depending on its current direction and the option Auto displays in the Display Orientation drop down list by default In addition the actu...

Страница 30: ...to 1 00 and click Apply Setting the 3 phase load out of balance threshold The threshold percentage specified determines when the current on the lines of a 3 phase system are out of balance between the three phases of power If the alerting feature is enabled an alert will be sent when an out of balance condition occurs In the 3 Phase Load Out of Balance Threshold field type a value from 0 to 100 an...

Страница 31: ...iptive outlet name Click on the Outlet Names link which will open the Outlets configuration page For more information about creating descriptive outlet names see the Outlets section Creating a descriptive serial port name Click on the Serial Port Names link which will open the Serial Ports configuration page Creating a descriptive environmental monitor name Click on the Environmental Monitor Names...

Страница 32: ...Address Subnet Mask and Gateway fields Enabling Dynamic Host Configuration Protocol DHCP To enable DHCP check the Enable checkbox To disable DHCP uncheck clear the checkbox Click Apply Setting the Fully Qualified Domain Name FQDN To enable the FQDN check the Enable checkbox and accept the default name sentry3 521384 or type a different name To disable the FQDN uncheck the checkbox Click Apply Enab...

Страница 33: ...pply Telnet SSH The Telnet SSH configuration page enables or disables Telnet and SSH support and configures the port number that the Telnet or SSH server watches Enabling or disabling Telnet or SSH support Select Enabled or Disabled from the appropriate Server drop down menu and click Apply Changing the Telnet or SSH server port number In the appropriate Port field enter the port number and click ...

Страница 34: ...ovide a passphrase 0 47 characters for the new certificate To change the passphrase type a new passphrase and check the Change checkbox Click Apply The Stored Files section displays a message to confirm the upload status of the user certificate and its related public key Custom User Certificate Messages Message Description and Valid Values Range Cert Key Both the user certificate and its key were ...

Страница 35: ...PM can re discover the device and add it to the system Once the unit has been acquired by SPM no further action is necessary To reset the password check SPM Password and click Apply NOTE Do not reset the password if SPM communication has already been established Serial Ports The Serial Ports configuration page allows maintenance to the serial port NOTE Pass Thru connections can only be initiated f...

Страница 36: ...d or Disabled from the SCP drop down menu and click Apply NOTES Upon a coldboot of the system if the Coldboot Alert feature is enabled the system will send a second RS 232 break out to any SCP enabled serial ports The SCP option must be enabled to use the Bluetooth Android solution Enabling or disabling the Serial Command Protocol SCP emulation This option notifies SCP of an MRV device on a specif...

Страница 37: ...Bluetooth module is never in discoverable mode Bluetooth Pin Code The pin code is available for legacy Bluetooth modules that require a pin to pair the module Although not used in current Bluetooth modules the pin code is supported if needed Default is 9611 must be 4 digits range is 0000 to 9999 Bluetooth Transmission Power Designated transmission power dbm for the Bluetooth module Note that lower...

Страница 38: ...Select the UPS manufacturer type from the Type drop down list type an IP address or hostname for the UPS and click Apply To edit the UPS type Under the Action heading click the Edit link for the UPS to be configured The Configuration UPS page reformats to an edit page where UPS device settings are configured and UPS devices are associated with an infeed Selecting the UPS type Select the UPS manufa...

Страница 39: ...ould not be turned on Click the Edit link in the Action column next to the outlet to be configured On the subsequent Outlet edit page check the Locked No Control checkbox to lock the outlet or uncheck the box to unlock the outlet and click Apply NOTE Outlets can only be locked and unlocked individually by outlet name there is no global outlet lock unlock command action When an outlet is configured...

Страница 40: ...t status and serial Pass Thru ports User Partial access for control On Off Reboot status and Pass Thru of assigned outlets groups and serial Pass Thru ports Reboot Only Partial access for control Reboot status and Pass Thru of assigned outlets groups and serial Pass Thru ports On Only Partial access for control On status and Pass Thru of assigned outlets groups and serial Pass Thru ports View Only...

Страница 41: ...d by the user and click Apply Adding and deleting group access Click on the Groups link in the Access column for the associated user On the subsequent User Groups page select or deselect group to be accessed by the user and click Apply Adding and deleting serial port access Click on the Ports link in the Access column for the associated user On the subsequent User Ports page select or deselect por...

Страница 42: ... filepath Enter the path of the file to be uploaded in the Directory field and click Apply Setting the filename for upload Enter the filename of the file to be uploaded in the Filename field and click Apply Testing the FTP upload configuration This test validates that the unit is able to contact and log onto the specified FTP server download the firmware file and verify that the firmware file is v...

Страница 43: ...e current DST settings To increment the settings based on updates to the start end day time options click Update Setting the SNTP primary secondary server address The Primary Secondary Host fields contact the SNTP server The fields are populated with the external NTP pool time zones 2 servertech pool ntp org and 1 servertech pool ntp org These are the default names for new PDUs that have not yet b...

Страница 44: ...ring is set to public and the SET community string is left blank Setting the SNMPv3 read write RW user or read only RO user Enter the Read Write User or Read Only User username and click Apply A valid username can be set to any value between 1 31 characters Configuring the SNMPv3 read write RW user or read only RO user authentication type From the Read Write User or Read Only User Authentication T...

Страница 45: ...elect the desired traps and click Apply Configuring input feed traps and thresholds Click on the Input Feed Traps and Thresholds link On the subsequent Input Feed Traps page select or deselect the desired traps and click Apply For Load traps enter a maximum load value for the infeed in the High Load Threshold field and click Apply The default input feed high load threshold is 80 of the input feed ...

Страница 46: ...g the authentication order Select Remote Local or Remote Only from the drop down menu and click Apply NOTE Server Technology recommends not setting the authentication order to Remote Only until LDAP has been configured and tested Setting the LDAP server address Enter the IP address or hostname in the Primary and or Secondary Host field and click Apply NOTE Both IPv4 and IPv6 formats are accepted i...

Страница 47: ...ng an LDAP group Enter a descriptive group name in the LDAP Group Name field Up to 24 alphanumeric and other typed characters ASCII 33 to 126 decimal are allowed spaces are not allowed Press Apply Removing an LDAP group Click on the Remove link in the Action column for the group to be removed and click OK on the subsequent confirmation window Changing an LDAP group s access privilege level Click o...

Страница 48: ...lect Remote Local or Remote Only from the drop down menu and click Apply For more information about remote authentication order see the Setting the authentication order section NOTE Server Technology recommends not setting the authentication order to Remote Only until TACACS has been fully configured and tested Setting the TACACS encryption key Enter a key and verify the new key the Encryption Key...

Страница 49: ... Adding and deleting outlet group access Click on the Groups link in the Access column for the associated TACACS Privilege Level On the subsequent LDAP Group Groups page select or deselect outlet groups to be accessed by the TACACS Privilege Level and click Apply Adding and deleting serial port access Click on the Ports link in the Access column for the associated TACACS Privilege Level On the sub...

Страница 50: ...nge the shared secret check the Change checkbox to clear the Shared Secret field enter the new shared secret and click Apply Changing the RADIUS server port This field specifies the port number used by the RADIUS server for incoming RADIUS authentication requests Enter the port number in the Primary and or Secondary Port field and click Apply The valid port number range is 1 65535 default is 1812 ...

Страница 51: ...ck Apply Setting the Email SMTP authentication username In the Username field type the desired Email SMTP username and click Apply Spaces are not allowed Setting the Email SMTP authentication password The Set Email SMTP Password command sets the password for SMTP authentication with the username In the Password field type a password of 1 16 alphanumeric and other characters ASCII 33 to 126 decimal...

Страница 52: ...rify the new password Press Apply Firmware The Firmware page allows the uploading of a system firmware bin file Click Browse to locate the bin firmware file and then click Upload A confirmation message is displayed View Log The View Log feature enables viewing of the internal system log This features logs all authentication attempts power actions configuration changes and other system events The s...

Страница 53: ...yed before the Switched CDU prompt You can enter commands in any combination of uppercase and lowercase All command characters must be entered correctly there are no command abbreviations A user must have administrative privileges to use the administration commands The following tables list and briefly describe each command Operations Command Summary Command Description Connect Connects to a seria...

Страница 54: ...ables the Cisco EnergyWise network Set EnergyWise Domain Sets the Cisco EnergyWise domain name Set EnergyWise Port Sets the Cisco EnergyWise port number Set EnergyWise Refresh Rate in seconds at which information is pushed to the EnergyWise manager Set EnergyWise Secret Sets the Cisco EnergyWise secret Set Envmon Name Specifies a descriptive field fro the integrated Environmental Monitor Set Envmo...

Страница 55: ...ru port Set Port Name Specifies a descriptive field for a serial Pass Thru port Set Port SCP Enables or disables Serial Command Protocol SCP functions Set Port SCP Emulate Notifies the Serial Command Protocol SCP of an MRV device on a specific serial port Set Port Speed Set the connection speed for all serial Pass Thru ports Set Port Timeout Sets the inactivity timeout period for a serial port bef...

Страница 56: ...ettings Show Options Displays system option information Show Outlets Displays configuration information for all outlets Show Ports Displays serial Pass Thru port configuration information Show SNTP Displays SNTP configuration information Show System Displays system configuration information Show System Status Displays system power and tower configuration information Show Towers Displays tower conf...

Страница 57: ...e displayed NOTE You will have to reissue the Status command to verify that the outlets have rebooted To reboot one or more outlets At the Switched CDU prompt type reboot followed by an outlet name and press Enter or Type reboot followed by a group name and press Enter or Type reboot all and press Enter Example The following command reboots all the outlets in the group named ServerGroup_1 Switched...

Страница 58: ...tatus for outlets in the group ServerGroup_1 Switched CDU status ServerGroup_1 Enter Group ServerGroup_1 Outlet Outlet Outlet Control ID Name State State A1 DataServer_1 On On A2 WebServer_1 On On A3 FileServer_1 On On Displaying accessible outlets The List Outlets command displays accessible outlets for the current user The display includes the absolute and descriptive name of all outlets assigne...

Страница 59: ...urrent user Switched CDU list ports Enter Port Port ID Name Console Console Displaying infeed status The Istat command displays the status of one or more infeeds This display includes the infeed absolute and descriptive names as well as the Input Status and current Load reported to the PDU by the infeed branch or phase To display status of one or more infeeds Type istat and press Enter Examples Th...

Страница 60: ...current user s password For security when you type a password the characters are not displayed on the screen For more information see the Usernames and Passwords section To change a password At the Switched CDU prompt type password and press Enter At the Enter Current Password prompt type the current password and press Enter At the Enter New Password prompt type the new password and press Enter Pa...

Страница 61: ...ion Creating a user account The Create User command creates a user account with the specified username and password See Usernames and Passwords in this chapter for more information To create a user account At the Switched CDU prompt type create user optionally followed by a 1 16 character username Spaces are not allowed and usernames are not case sensitive Press Enter At the Password prompt type a...

Страница 62: ...have more than one administrative level user NOTE You cannot remove administrative access from the default admn user unless you have already granted administrative access to another user account To set the access level privilege for a user At the Switched CDU prompt type set user access followed by admin poweruser user rebootonly ononly or viewonly optionally followed by a username and press Enter...

Страница 63: ... all followed by a username and press Enter Examples The following commands grant the user JaneDoe access to outlets A1 and Webserver_1 Switched CDU add outlettouser a1 janedoe Enter Switched CDU add outlettouser WebServer_1 janedoe Enter Deleting outlet access for a user The Delete OutletFromUser command removes a user s access to one or all outlets You cannot remove access to any outlet for an a...

Страница 64: ...al port for an administrative level user To delete serial port access for a user At the Switched CDU prompt type delete portfromuser console and a username Press Enter Displaying user outlet group and serial port access The List User command displays all accessible outlets groups and serial ports for a user To display user outlet group and serial port access At the Switched CDU prompt type list us...

Страница 65: ...et outlet name a1 DataServer_1 Enter Setting the outlet wakeup state The Set Outlet Wakeup command set the default wakeup state for that outlet In the event of a system wide power loss this state will be applied to the outlet when power is restored The wakeup state can be set to On Off or Last Upon restoration of system power If set to On the PDU will apply power to that outlet If set to Off the P...

Страница 66: ... by yes and press Enter Example The following command locks outlet TowerA_InfeedA_Outlet1 Switched CDU set outlet locked TowerA_InfeedA_Outlet1 yes Enter When an outlet is configured into the locked state the outlet will lock at its current control state On or Off The outlet control state will then change to Locked On or Locked Off The locked control state Yes or No displays in the outlets list us...

Страница 67: ...9 On 0 No A10 TowerA_Outlet10 On 0 No A11 TowerA_Outlet11 On 0 No A12 TowerA_Outlet12 On 0 No A13 TowerA_Outlet13 On 0 No A14 TowerA_Outlet14 On 0 No A15 TowerA_Outlet15 On 0 No A16 TowerA_Outlet16 On 0 No More Y es N o Outlet Options Sequence Interval 2 seconds Reboot Delay 15 seconds Input Feed Administration Creating a descriptive infeed name The Set Infeed Name command assigns a descriptive na...

Страница 68: ... about all infeeds This information includes the absolute and descriptive infeed names operational voltages and maximum load capacities To display tower information At the Switched CDU prompt type show infeeds and press Enter Example Switched CDU show infeeds Enter Input Input Input Input Feed ID Feed Name Feed Voltage Feed Capacity Amps AA HQ_1_Infeed_A 100 15 AB HQ_1_Infeed_B 120 20 BA HQ_2_Infe...

Страница 69: ...o CW 8H1 C20 Switched CDU set tower prodsn a CW 8H1 C20 Enter Setting the tower AC or DC voltage type The Set Tower command is used to set the product input AC or DC voltage type NOTE If set at the factory you cannot edit the voltage type To set the tower AC DC voltage type At the Switched CDU prompt type set tower followed by ac or dc and the absolute tower name Press Enter Example The following ...

Страница 70: ...roup name The Create Group command creates a new group name To create a group name At the Switched CDU prompt type create group optionally followed by a descriptive name of up to 24 alphanumeric and other typed characters ASCII 33 to 126 decimal are allowed spaces are not allowed Group names are not case sensitive Press Enter Example The following command creates group name ServerGroup_1 Switched ...

Страница 71: ...rverGroup_1 Enter The following commands use the outlets descriptive names to add outlets DataServer_1 and WebServer_1 to group name ServerGroup_1 Switched CDU add OutletToGroup DataServer_1 ServerGroup_1 Enter Switched CDU add OutletToGroup WebServer_1 ServerGroup_1 Enter The following command add all outlets to group name ServerGroup_1 Switched CDU add OutletToGroup Enter Outletname all Enter Gr...

Страница 72: ..._1 to the second temperature humidity sensor Switched CDU set envmon ths name a2 T H2_Florida_HQ_1 Enter Serial Port Administration Creating a descriptive serial port name The Set Port Name command assigns a descriptive name to a serial port You can use this name in commands that require a port name as an alternative to using the port s absolute name To create an port name At the Switched CDU prom...

Страница 73: ...ule name cannot be blank At the Switched CDU prompt type set bluetooth name followed by 1 31 characters of a descriptive name for the module and press Enter To set the Bluetooth discoverability Three discoverability settings determine the current status of the pushbutton on the Bluetooth module Always The Bluetooth module is discoverable even without pressing the pushbutton Limited Default The pus...

Страница 74: ...e or MRV and press Enter Enabling or disabling the RFTAG option This option makes RF Code sensor tags available for the Server Technology wireless monitoring solution To enable or disable the RF Code sensor options At the Switched CDU prompt type set port rftag follow by the serial port name followed by enabled or disabled and press Enter Displaying serial port information The Show Ports command d...

Страница 75: ...To create a location description At the Switched CDU prompt type set location followed by a descriptive name of up to 24 alphanumeric and other typed characters ASCII 33 to 126 decimal are allowed spaces are allowed Press Enter Omitting any characters after typing set location deletes any previously specified text Examples The following command specifies Florida HQ as the descriptive location for ...

Страница 76: ...of balance alert The Set System Balance Alert command enables or disables the sending of an alert when the current on the lines of a 3 phase system are past a pre set threshold percentage and are out of balance between the three phases of power At the Switched CDU prompt type set system balancealert followed by enabled or disabled and press Enter Example The following command enables the load out ...

Страница 77: ...inutes 1 second Location Florida HQ Area Footprint 6 3 square feet Power Factor 0 80 3 Phase Load Out of Balance Threshold 20 percent Alerting Enabled Displaying system power status The System Status command displays system power and tower information To display system power status At the Switched CDU prompt type sysstat and press Enter Example Switched CDU sysstat System Power Status Total Power ...

Страница 78: ...tched CDU prompt type set option strong password followed by enabled or disabled and press Enter Enabling or disabling the external configuration reset button The Set Option Button command enables or disables the external configuration reset button This feature can enhance system security by protecting the PDU configurations from being reset locally NOTE If this feature has been enabled and the ad...

Страница 79: ...ion timeout in minutes and press Enter Example The following command sets the web session Web Interface timeout to 10 minutes Switched CDU set option webtimeout 10 Enter Customizing the CLI prompt The Set Option Prompt command customizes the CLI prompt To customize the CLI prompt At the Switched CDU prompt type set option prompt and press Enter Then type the custom prompt and press Enter To reset ...

Страница 80: ...nd displays settings for all system options To display system option information At the Switched CDU prompt type show options and press Enter Example Switched CDU show options System Options Display Orientation Auto Normal Outlet Sequence Order Normal Strong Passwords Disabled Configuration Reset Button Enabled More Prompt Enabled Temperature Scale Celsius CLI Custom Prompt none CLI Session Timeou...

Страница 81: ...secret The Set EnergyWise Domain command configures the EnergyWise domain the PDU belongs to The limit of the Domain Name is 64 characters To set the EnergyWise domain name At the Switched CDU prompt type set energywise domain followed by the domain name and press Enter Example Switched CDU set energywise domain 10 1 2 120 Command successful To set the EnergyWise port The default port number is 43...

Страница 82: ... EnergyWise refresh rate is the rate in seconds at which new information is pushed to the EnergyWise manager Valid range is 30 600 seconds default is new data sent to the EnergyWise manager every 3 minutes At the Switched CDU prompt type set energywise refresh followed by a rate in seconds from 30 600 and press Enter Viewing Cisco EnergyWise network parameters NOTE A change in any value shown in t...

Страница 83: ...tdelay followed by enabled or disabled and press Enter NOTES The Boot Delay option executes only when DHCP is enabled The firmware can detect network link integrity and will wait for network connection This means that if the network is not currently connected the enabled Boot Delay option will be ignored Enabling or disabling DHCP static address fallback NOTE DHCP must be enabled to activate the D...

Страница 84: ...Enter Example The following command set the gateway IP address to 12 34 56 1 Switched CDU set gateway 12 34 56 1 Enter Setting the DNS IP address The Set DNS command sets the TCP IP address of the Domain Name server DNS To set the DNS IP address At the Switched CDU prompt type set followed by dns1 or dns2 and the Domain Name server s IP address Press Enter NOTE Both IPv4 and IPv6 formats are accep...

Страница 85: ... 2 253 Subnet Mask 255 255 0 0 IPv4 Gateway 10 1 1 1 DNS1 10 1 5 133 DNS2 10 1 5 134 DHCP Settings DHCP Enabled FQDN Enabled sentry3 524104 Boot Delay Enabled Static Fallback Enabled Network Services Telnet Enabled Port 23 SSH Enabled Port 22 Auth Password Kb Int HTTP Enabled Port 80 SSL Enabled Port 443 Access Optional SNMPv1 2 Enabled Port 161 TrapPort 162 SNMPv3 Disabled Port 161 TrapPort 162 F...

Страница 86: ... If your operation does not currently use SPM software you can disable SPM Secure Access However if disabled the PDU will not be able to use the SPM suite of secure network capabilities or the advanced remote configuration To enable or disable SPM support At the Switched CDU prompt type set spm followed by enabled or disabled and press Enter NOTE Both HTTP and SSL must be enabled or the SPM Secure...

Страница 87: ...irmware improvements and new features additions The following commands are used to configure the PDU for an FTP firmware upload For more information about initiating an FTP firmware upload see Appendix B NOTE Secure File Transport Protocol SFTP is also supported for encrypted SSH transport over the network Setting the FTP host address The Set FTP Host command sets the FTP host IP address or hostna...

Страница 88: ...FTP directory to ftp Sentry Switched CDU set ftp directory ftp sentry Enter Enabling or disabling automatic updates The Set FTP Autoupdate command is used to enable or disable automatic firmware update support To enable or disable automatic updates At the Switched CDU prompt type set ftp autoupdate followed by enabled or disabled and press Enter Setting the automatic update scheduled day The Set F...

Страница 89: ...ration Host 10 1 2 100 Username djones Password Directory firmware 7 0d Filename smcdu v70d bin FTP Automatic Updates Configuration Automatic Updates Disabled Scheduled Day Everyday Scheduled Hour 1 PM SNTP Administration The firmware supports the use of a network time service to provide a synchronized time reference About Daylight Saving Time DST Support for DST is disabled by default When enable...

Страница 90: ...tting the local GMT offset hours minutes The Set SNTP GMToffset command sets the offset from GMT for the date time returned by SNTP The GMT offset supports all standard international time zones from 12 59 to 14 59 The GMT offset can be set in minutes to accommodate partial hour time zones NOTE The PDU does not support automatic adjustment for Daylight Saving Time DST To set the local GMT offset At...

Страница 91: ...PS record for a Toshiba UPS with the hostname DC1Toshiba1 Switched CDU create ups Enter UPS types 1 Generic RFC1628 2 Liebert 3 MGE 4 Tripp Lite 5 APC 6 HP 7 Minuteman 8 Mitsubishi 9 Powerware 10 Toshiba 11 Falcon Electric Select type 1 11 10 Enter Host IP DC1Toshiba1 Enter Removing a UPS record The Remove UPS command removes a UPS record To remove a UPS record At the Switched CDU prompt type remo...

Страница 92: ... 8 2 Enter UPS types 1 APC 2 Liebert 3 MGE 4 Tripp Lite 5 Generic RFC1628 6 Hewlett Packard 7 Minuteman 8 Mitsubishi 9 Powerware 10 Toshiba 11 Falcon Electric Select type 1 11 3 Enter Changing the UPS host address The Set UPS Host command is used to change the IP address or hostname for each UPS record Hostnames can be up to 60 characters long To change a UPS host address At the Switched CDU promp...

Страница 93: ... configured on the UPS To change a UPS SNMP community string record At the Switched 48 VDC prompt type set ups commstr and press Enter At the prompt type the index number for the UPS record to be changed and press Enter At the prompt type the Get community string for the UPS and press Enter Example The following command changes Get community string for the record at index number 2 to readonly Swit...

Страница 94: ...set ups addinfeed Enter UPS UPS Infeed Index Type IDs 1 Liebert 2 MGE AA Select UPS 1 8 1 Enter Infeed ID aa Enter Removing an infeed from a UPS The Set UPS DelInfeed command removes a logical association of an infeed from a UPS To remove an infeed from a UPS At the Switched CDU prompt type set ups delinfeed and press Enter At the prompt enter the index number for the UPS record to be changed and ...

Страница 95: ...1Liebert1 Voltage Polling ON SNMP Configuration Community String public SNMP Port 162 SNMP Objects Expected Values Voltage 1 3 6 1 2 1 33 1 4 4 1 2 1 Utility Status 1 3 6 1 2 1 33 1 4 1 0 On Battery 0x5 On Utility 0x3 More Y es N o Feature Administration Displaying activated special features The Show Features command displays all activated special features for the device To display activated speci...

Страница 96: ......

Страница 97: ... 116 Enabling and setting up LDAP support 117 Configuring LDAP Groups 121 TACACS 126 Enabling and setting up TACACS support 126 Configuring TACACS privilege levels 128 TACACS Technical Specifications 131 RADIUS 132 Enabling and Setting Up RADIUS Support 132 Vendor Specific Attributes VSA 135 LOGGING 136 Internal System Log 136 Syslog 136 Email 138 UPLOAD DOWNLOAD 141 Integrated FTP Server 141 FTP ...

Страница 98: ...he SSL port number Set SSL User Certificate Enables disables custom user certificates Set SSL User Passphrase Passphrase to control login access for user certificates Enabling and Setting Up SSL Support NOTE A restart of the PDU is required after setting or changing any SSL configurations Enabling or disabling SSL support The Set SSL command enables or disables SSL support To enable or disable SSL...

Страница 99: ...ntication of uploaded custom user certificates To set the user certificate passphrase At the Switched CDU prompt type set ssl userpass and press Enter You will be prompted to provide the passphrase Press Enter NOTE A restart of the PDU is required after setting the user certificate passphrase SSL Technical Specifications Secure Socket Layer SSL Transport Layer Security TLS version 1 RFC 2246 SSL T...

Страница 100: ... number Enabling and Setting up SSH Support NOTE A restart of the PDU is required after setting or changing any SSH configurations Enabling or disabling SSH support The Set SSH command is used to enable or disable SSH support To enable or disable SSH support At the Switched CDU prompt type set ssh followed by enabled or disabled and press Enter Changing the SSH server port With SSH support enabled...

Страница 101: ...ymmetric Cryptography Diffie Hellman DSA DSS 512 1024 random bits per NIST specification Symmetric Cryptography AES256 CBC RIJNDAEL256 CBC 3DES 192 CBC AES192 CBC RIJNDAEL192 CBC AES128 CBC RIJNDAEL128 CBC Message Integrity HMAC SHA1 160 HMAC MD5 128 Authentication Username Password Session Channel Break Extension for RS232 Break ...

Страница 102: ...3 All SNMP v1 v2 specific configuration settings use the CLI command SET SNMP V2 All SNMP configuration settings common to any SNMP version use the CLI command SET SNMP NOTES If you use SNMP v1 or SNMP v2 all SET SNMP CLI commands and the SHOW command require the V2 keyword SNMP v1 v2 CLI commands are documented immediately below in this section showing the required V2 keyword All CLI commands tha...

Страница 103: ... snmp v2 getcomm followed by the string and press Enter Displaying SNMP v1 v2 configuration information The Show SNMP V2 command displays all SNMP v1 v2configuration information including SNMP support status SNMP community strings Trap timer value Trap destinations both IPv4 and IPv6 formats can be displayed To display SNMP v1 v2 configuration information At the Switched CDU prompt type show snmp ...

Страница 104: ...d OID are available on the Server Technology website ftp ftp servertech com pub SNMP sentry3 Technical support is available 8 00AM to 5 00 PM Pacific Time Monday Friday For SNMP Support email mibmaster servertech com Enabling and Setting up SNMP Support SNMP support must be enabled and configured for access to Sentry3 MIB objects and generation of all Sentry3 traps Enabling disabling SNMP support ...

Страница 105: ...hed CDU prompt type set snmpv3 rwusername and press Enter NOTE You can set a blank username but doing so will clear the string and disallow any read write user access Setting the SNMP v3 read write RW authentication type The Set SNMP RW Auth Type command sets the SNMP v3 RW authentication type To set the RW authentication type At the Switched CDU prompt type set snmp v3 rwauthtype followed by none...

Страница 106: ...ardless of the versions that are enabled for the agent Example The following sets the trap format version to SNMP v3 Switched CDU set snmp trapformat 3 Enter Setting IP Restrictions The Set SNMP IP Restrictions command supports SNMP Manager Get and Set requests to only be allowed from the IP address of the defined trap destinations To set SNMP IP restrictions At the Switched CDU prompt type set sn...

Страница 107: ...ublic To set the Getcomm community string At the Switched CDU prompt type set snmp getcomm followed by the string and press Enter Setting the SNMP SysName The Set SNMP SysName command is used to set the SNMP MIB II SysName object To set the SysName object At the Switched CDU prompt type set snmp sysname followed by the object name and press Enter Setting the SNMP SysLocation The Set SNMP SysLocati...

Страница 108: ...and press Enter Example The following command displays the SNMP configuration information Switched CDU show snmp Enter SNMP Configuration SNMPv2 Agent Enabled GET Community RO public SET Community RW undefined TRAP Community trap SNMPv3 Agent Disabled Engine ID 800006B602000000000000000000000FFFF0A010249 RW Username undefined RW Auth Type None password not set RW Privacy Type None password not set...

Страница 109: ...s generated at the end of every timer period until the Status returns to a non error status All status traps are enabled by default Tower Status Traps Status Error Description Normal Tower is working correctly NoComm x Communication to the tower has been lost Infeed Status Traps Status Error Description On Infeed is on OffError x Infeed should be on but no current is sensed at the infeed NoComm x ...

Страница 110: ...n infeed exceeds a preset threshold Load traps include the reported input load load status Location of the PDU and identifier and name of the affected infeed Any error state generates a Load trap and triggers the trap timer A new trap is generated at the end of every timer period until the Load returns to a non error status Load traps Status Error Description Normal Infeed is on and within preset ...

Страница 111: ...n lost Configuring Traps SNMP Trap Command Summary Command Description Set Trap Tower Status Enables or disables the Tower Status trap Set Trap Infeed Status Enables or disables the Infeed Status trap off Set Trap Infeed Load Enables or disables the Infeed Load trap Set Trap Infeed Highthresh Sets the Infeed Load trap high limit Set Trap Outlet Change Enables or disables the Outlet Change trap Set...

Страница 112: ...bled Enabling or disabling a load trap The Set Trap Infeed Load command is used to enable or disable an Infeed Load trap To Enable or Disable a Load trap At the Switched CDU prompt type set trap infeed load followed by the infeed name and on or off Press Enter or Type set trap infeed load all followed by on or off and press Enter Examples The following command enables the Load trap for second infe...

Страница 113: ...sor Switched CDU set trap ths temp a1 on Enter Setting the temperature sensor threshold limits The Set Trap THS Templow and Set Trap THS Temphigh commands are used to set the lower and upper threshold limits for the Temperature sensor To set the Temperature threshold limits At the Switched CDU prompt type set trap ths templow or temphigh followed by the sensor name and a value from 0 to 123 in deg...

Страница 114: ...ture humidity sensor A1 Switched CDU set trap ths humiddelta temp_humid_sensor_A1 2 Enter Enabling or disabling the humid trap The Set Trap THS Humid command is used to enable or disable the Humid trap To Enable or Disable the Humid trap At the Switched CDU prompt type set trap ths humid followed by the sensor name and on or off Press Enter Example The following command enables the Humid trap for ...

Страница 115: ...A ON ON 255 A BA HQ_2_Infeed_A ON ON 255 A More Y es N o y Outlet trap configuration Outlet Outlet Stats Change ID Name Trap Trap AA1 DataServer_1 ON OFF AA2 WebServer_1 ON OFF AA3 FileServer_1 ON OFF AA4 ON OFF AA5 ON OFF AA6 ON OFF AA7 ON OFF AA8 ON OFF AB1 ON OFF AB2 ON OFF AB3 ON OFF AB4 ON OFF AB5 ON OFF AB6 ON OFF AB7 ON OFF AB8 ON OFF More Y es N o y Environmental Monitor A trap configurati...

Страница 116: ...elete PortfromLDAP Removes access to one or more serial ports for an LDAP group List LDAPGroup Displays all accessible outlet groups ports for an LDAP group List LDAPGroups Displays privilege levels for all LDAP groups Ping Verifies proper DNS configuration by name resolution Remove LDAPGroup Deletes an LDAP group name Set Authorder Specifies the authentication order for each new session attempt S...

Страница 117: ...ble or disable LDAP support At the Switched CDU prompt type set ldap followed by enabled or disabled and press Enter Setting the LDAP host address The Set LDAP Host command sets the TCP IP address of the Directory Services server NOTE Both IPv4 and IPv6 formats are accepted for hostname To set the LDAP host address At the Switched CDU prompt type set ldap followed by host1 or host2 and the Directo...

Страница 118: ...d will be attempted This field is used only with Simple binds To set the search bind DN At the Switched CDU prompt type set ldap binddn and press Enter At the following prompt type the FQDN and press Enter Example The following sets the FQDN for MSAD to cn guest cn Users dc servertech dc com Switched CDU set ldap binddn Enter Enter Search Bind DN Max characters 124 cn guest cn Users dc servertech ...

Страница 119: ...de all subtrees Maximum size is 100 characters To set the user search base DN At the Switched CDU prompt type set ldap userbasedn and press Enter At the following prompt type the search base DN and press Enter Example The following sets the DN user search base for MSAD to cn Users dc servertech dc com Switched CDU set ldap userbasedn Enter Enter User Search Base DN Max characters 100 cn Users dc s...

Страница 120: ...or remoteonly and press Enter NOTE Server Technology recommends not setting the authentication order to Remote Only until the LDAP has been fully configured and tested Displaying LDAP configuration information The Show LDAP command displays LDAP configuration information Enabled disabled status of LDAP support Directory Services server IP address and port Bind request password type and remote auth...

Страница 121: ...he Directory Services server previously configured and press Enter Example The following command verifies the DNS configuration Switched CDU ping servertech com Pinging servertech com 98 76 54 32 with 64 bytes of data Reply from 98 76 54 32 bytes 64 pseq 0 triptime 0 Reply from 98 76 54 32 bytes 64 pseq 1 triptime 0 Reply from 98 76 54 32 bytes 64 pseq 2 triptime 0 Reply from 98 76 54 32 bytes 64 ...

Страница 122: ...ants input status viewing privileges to the LDAP group PowerUser Switched CDU set ldapgroup envmon on poweruser Enter NOTE Granting access to environmental monitoring temperature humidity sensors to a non admin user also grants that user access to power monitoring outlets infeeds towers all environmental data of the PDU Granting and removing input status viewing privileges The Set LDAPGroup Envmon...

Страница 123: ...tlet group To grant access for more than one outlet group you must use multiple Add GroupToLDAP commands To grant outlet group access to an LDAP Group At the Switched CDU prompt type add grouptoldap optionally followed by an outlet group name and an LDAP group name Press Enter Examples The following commands grants to LDAP group PowerUser access to the outlet groups ServerGroup_1 and ServerGroup_2...

Страница 124: ...isplays information about the LDAP group PowerUser Switched CDU list ldapgroup poweruser Enter Username PowerUser Outlet Outlet ID Name A1 DataServer_1 A2 WebServer_1 Groups ServerGroup_1 ServerGroup_2 More Y es N o Y Ports Port Port ID Name Console Console Members of the PowerUser LDAP group can access the following outlets outlet groups and serial ports outlet A1 which has a descriptive name of ...

Страница 125: ...d Successful Bind Attribute match Username found Attribute name compared to Group Membership Attribute Subtree search starting from User Search Base DN with User Search Filter Prompt for login credentials Simple Bind using User FQDN and login password Simple bind using Search Bind DN Password Subtree search starting from User Search Base DN with User Search Filter Access Denied Username groups acc...

Страница 126: ...key Set TACACS Port Sets the TACACS server port number Show TACACS Displays TACACS configurations Add GrouptoTACACS Grants a TACACS account access to one or more groups Add OutlettoTACACS Grants a TACACS account access to one or more outlets Add PorttoTACACS Grants a TACACS account access to one or more serial ports Delete GroupfromTACACS Removes access to one or more groups for a TACACS account D...

Страница 127: ...server To set the encryption key At the Switched CDU prompt type set tacacs key and press Enter At the TACACS Key prompt type an encryption key of up to 60 alphanumeric and other typed characters ASCII 33 to 126 decimal are allowed encryption keys are case sensitive Press Enter To specify no password press Enter At the Verify TACACS Key prompt retype the key Press Enter To verify no password press...

Страница 128: ...gured and tested Displaying TACACS configuration information The Show TACACS command displays TACACS configuration information To display the TACACS configuration information At the Switched CDU prompt type show tacacs and press Enter Example The following command displays the TACACS configuration information Switched CDU show tacacs Enter TACACS Configuration TACACS Enabled Host 1 98 76 54 32 Hos...

Страница 129: ... monitoring The Set TacPriv Envmon command grants or removes input status viewing privileges to from a TACACS account To grant or remove input status viewing privileges for a TACACS account At the Switched CDU prompt type set tacpriv envmon followed by on or off optionally followed by a TACACS account number and press Enter Example The following command grants input status viewing privileges to th...

Страница 130: ...t number 5 access to the outlet groups ServerGroup_1 and ServerGroup_2 Switched CDU add grouptotacacs servergroup_1 5 Enter Switched CDU add grouptotacacs servergroup_2 5 Enter Deleting outlet group access for a TACACS account The Delete GroupFromTACACS command removes a TACACS account s access to an outlet group You cannot remove access to any group for an administrative level account To delete o...

Страница 131: ...oup ServerGroup_1 group ServerGroup_2 and Console serial port TACACS Technical Specifications Authentication START Packet includes action 1 TAC_PLUS_AUTHEN_LOGIN priv_lvl 0 TAC_PLUS_PRIV_LVL_MIN authen_type 1 TAC_PLUS_AUTHEN_TYPE_ASCII service 1 TAC_PLUS_AUTHEN_SVC_LOGIN user entered username port access path into the unit rem_addr Sentry3_xxxxxx xxxxxx is last six digits of MAC address data null ...

Страница 132: ...S server Set RADIUS Port Sets the port number of the RADIUS server Set RADIUS Timeout Configures the timeout interval for the RADIUS server Set RADIUS Retries Sets the number of retries for the RADIUS server Show RADIUS Displays RADIUS configuration settings Enabling and Setting Up RADIUS Support The following configuration tasks are required to properly enable and set up RADIUS support on the pri...

Страница 133: ...ecret Press Enter Enter the shared secret and press Enter For security shared secret characters are not displayed The secret that was set for the primary server will not be cleared when setting the secret for the secondary server and vice versa Changing the RADIUS port number The Set RADIUS Port command sets the server port number for RADIUS authentication requests To change the port number At the...

Страница 134: ...etries and press Enter The valid retries range is 0 10 default is 2 Examples The following command sets the retries for the primary RADIUS server to 5 Switched CDU set radius primary retries 5 Enter The following command sets the retries for the secondary RADIUS server to 2 Switched CDU set radius secondary retries 2 Enter Displaying RADIUS configuration information The Show RADIUS command display...

Страница 135: ...r access rights to groups of outlets values are space delimited strings of absolute IDs names or the special keyword ALL String values are case sensitive and limited to 253 characters This attribute can be repeated to append strings that declare additional access rights For STI Access Level values other than 1 Admn and 2 Power User if STI Groups is not included for a user the default is no group S...

Страница 136: ...red in the local memory and has support for up to 4097 continuously aging entries Viewing the internal system log The Show Log command allows users with administrative access to view the internal system log To view the internal system log At the Switched CDU prompt type show log and press Enter Example Switched CDU show log 1 EVENT System boot complete 2 EVENT TCP IP stack has started 3 Jul 24 18 ...

Страница 137: ...quests on the default Syslog port number 514 You can change this port number using the Set Syslog Port command To change the Syslog port At the Switched CDU prompt type set syslog port followed by the port number and press Enter Example The following changes the Syslog port number to 411 Switched CDU set syslog port 411 Enter Displaying Syslog configuration information The Show Syslog command disp...

Страница 138: ...thentication with username Set Email SMTP Use From Address Uses the SMTP From address for SMTP authentication Set Email SMTP Username Sets the username for SMTP authentication Set Email SMTP Useusername Uses the SMTP username password for SMTP authentication Show Email Displays all Email configuration information Enabling or disabling Email notification support The Set Email command enables or dis...

Страница 139: ...econdaryto and the destination email address Press Enter If the primary send to address fails the system then attempts to send the email to the secondary send to address Examples The following command sets the primary to email address to DayAdmin servertech com Switched CDU set email primaryto DayAdmin servertech com Enter The following command sets the secondary to email address to NiteAdmin serv...

Страница 140: ...Enter Sending a test email The Set Email Test command sends a test email to the target email destinations At the Switched CDU prompt type set email test and press Enter Displaying Email configuration information The Show Email command displays Email configuration information To display the Email configuration information At the Switched CDU prompt type show email and press Enter Example The follow...

Страница 141: ...le the integrated FTP server To enable or disable the FTP server At the Switched CDU prompt type set ftp server followed by enabled or disabled and press Enter FTP Configuration Files The FTP server supports upload download of two configuration files CONFIG BIN and NETWORK INI These files can be uploaded or downloaded using FTP PUT and GET operations CONFIG BIN This file contains the entire config...

Страница 142: ... to close the connection to the PDU FTP close PUTting a configuration file Upload NOTE Uploading the CONFIG BIN file takes considerably longer than the NETWORK INI file When uploading both Server Technology recommends uploading the NETWORK INI file first 1 Open the FTP client In a Windows environment in the Run window type ftp and press Enter 2 At the prompt type open followed by the IP address of...

Страница 143: ...ower from the outlet such as Off and Reboot commands 1 Off or Reboot command received by the PDU 2 Shutdown signal is sent to the Remote Shutdown Agent on the target server 3 Remote Shutdown Agent initiates a graceful shutdown of the target server and includes the ability to execute user defined scripts to perform custom activities such as safely shutting down open databases 4 The PDU removes powe...

Страница 144: ...a shutdown signal to the server Linux 1 Browse to the location of the Remote Shutdown Agent install files 2 Run SetupRA 3 For additional security when prompted enter the IP address of the PDU that will be sending the shutdown signal NOTE If left blank any PDU can send a shutdown signal to the server Unix 1 Browse to the location of the Remote Shutdown Agent install files 2 Run Install 3 For additi...

Страница 145: ...let Shutdown Delay command sets the Remote Shutdown delay for an outlet To set the Remote Shutdown delay At the Switched CDU prompt type set outlet shutdown delay followed by the outlet ID and a value from 1 to 900 in seconds Press Enter Example The following command sets the Remote Shutdown delay for outlet a2 to 120 seconds Switched CDU set outlet shutdown delay a2 120 Enter Setting the outlet h...

Страница 146: ... information The Show Shutdown command displays all shutdown configuration information Outlet ID and descriptive name Remote Shutdown settings Shutdown script setting To display shutdown information At the Switched CDU prompt type show shutdown and press Enter Example The following command displays all shutdown information Switched CDU show shutdown Outlet Outlet Name Shutdown Script ID Hostname I...

Страница 147: ...t web settings will be required From the Web interface On the Restart page in the Tools section of the Web interface select Restart and reset to factory defaults from the drop down menu and click Apply From the command line At the Switched CDU prompt type restart factory and press Enter Using the reset button Locate the recessed reset button directly beside the Serial Ethernet ports You will need ...

Страница 148: ...ng a command or from the Web interface Upon initiating an FTP upload session the unit will restart and upload the firmware file specified with the FTP Filename command from the previously configured FTP Host You must have administrator level privileges to initiate an upload Initiate an FTP upload session from the Web interface On the Restart page in the Tools section of the Web interface select Re...

Страница 149: ... Breaker If a circuit breaker is tripped it can be reset by pressing or switching it back ON once the cause of the overload or short circuit has been identified removed or resolved Intelligent PDUs with branch circuit sensing will display a flashing FE on the input current LED s to indicate Fuse Error Alternatively the circuit breaker can be turned OFF manually by inserting a slotted or flat blade...

Страница 150: ...g will display a flashing FE on the input current LEDs to indicate Fuse Error To service the fuse or turn OFF the branch rotate the Switch Handle toward the Fuse Access Door Next rotate the Fuse Access Door counter clock wise until it opens Only replace the fuse with the same size type and ratings as the original fuse Reverse these steps after the new fuse s is installed CAUTION Failure to replace...

Страница 151: ...ize type and ratings will damage the PDU and the connected and nearby equipment and will cause electrical shock fire explosion or injury death Time Delay Fuses Class G NOTE Server Technology PDUs ship with Bussman SC 20 fuses Ampere Rating Voltage Interrupting Rating Bussman Part No Server Technology Part No 20 A 600 Vac 100 000 A RMS Sym AC SC 20 FUSE SC20G Cooper Bussman Technical Data Sheet 102...

Страница 152: ...r direct local access or from other serial devices such as a terminal server An RJ45 crossover cable is provided for connection to an RJ45 DCE serial port Pin DTE Signal Name Input Output 1 Request to Send RTS Output 2 Data Terminal Ready DTR Output 3 Transmit Data TD Output 4 Signal Ground 5 Signal Ground 6 Receive Data RD Input 7 Data Set Ready DSR Input 8 Clear to Send CTS Input 6 7 54321 8 ...

Страница 153: ...rted in amperes and is displayed in 1 8 or 0 1 amp increments under 10A and whole amp increments at and above 10A Additionally the LED can display codes for events detected by the system for immediate local notification Behavior Code Event description Blinking The unit blinks half second on half second off when the current exceeds the user defined high load or factory default threshold 80 of maxim...

Страница 154: ... sur le matériel brouilleur du Canada European Union Notification Products with the CE Marking comply with both the EMC Directive 89 336 EEC and the Low Voltage Directive 73 23 EEC issued by the Commission of the European Community Compliance with these directives implies conformity to the following European Norms EN55022 Electromagnetic Interference EN55024 Electromagnetic Immunity EN60950 1 Prod...

Страница 155: ...applicable regulations and authorities within your region to ensure proper disposal Waste Electrical and Electronic Equipment WEEE In the European Union this label indicates that this product should not be disposed of with household waste It should be deposited at an appropriate facility to enable recovery and recycling ...

Страница 156: ...ee Technical Support is provided from 8 a m to 5 p m PST Monday through Friday After hours service is provided to ensure your requests are handled quickly no matter what time zone or country you are located in Server Technology Inc 1040 Sandhill Drive Tel 1 800 835 1515 Web www servertech com Reno Nevada 89521 USA Fax 775 284 2065 Email support servertech com Return Merchandise Authorization If yo...

Страница 157: ......

Отзывы: