Appendices
Switched PDU
Installation and Operations Manual
Compact Fuse Holder
The Compact Fuse Holder is a UL 98 listed Fused Disconnect Switch that allows the user to turn OFF the branch
circuit and safely service the fuse without having to disconnect the PDU AC power source prior to performing this
operation.
To help identify which fuse is open, blown, or missing, the Open Fuse
Indicator Light glows
orange
when the PDU is powered and the Switch
Handle is in the ON position.
Additionally, intelligent PDUs with branch circuit sensing will display a
flashing
FE
on the input current LEDs to indicate
Fuse Error
.
To service the fuse or turn OFF the branch, rotate the Switch
Handle toward the Fuse Access Door.
Next, rotate the Fuse Access Door counter clock-wise until it
opens.
Only replace the fuse with the same size, type, and ratings as the
original fuse.
Reverse these steps after the new fuse(s) is installed.
CAUTION:
Failure to replace the fuse with the same size, type, and ratings will damage the PDU and the connected and nearby
equipment, and will cause electrical shock, fire, explosion, or injury/death.
Do not attempt to open the Fuse Access Door without first setting the Switch Handle in the OFF position. Forcibly
rotating the Fuse Access Door will damage the fused holder.