![Server Technology Switched Rack PDU Скачать руководство пользователя страница 131](http://html1.mh-extra.com/html/server-technology/switched-rack-pdu/switched-rack-pdu_installation-and-operation-manual_1246861131.webp)
Switched PDU
Installation and Operations Manual
Advanced Operations
131
Displaying TACACS account access:
The List TacPriv command displays all access rights for a account.
To display TACACS account access:
At the Switched CDU: prompt, type
list tacpriv
, optionally followed by a account. Press
Enter
.
Example
The following command displays information about the account 1:
Switched CDU: list tacpriv 1<Enter>
Privilege Level: 1
Outlet Outlet
ID Name
.A1 DataServer_1
.A2 WebServer_1
Groups:
ServerGroup_1
ServerGroup_2
More (Y/es N/o): Y
Ports:
Port ID Port Name
Console Console
Members of the TACACS privilege level 1 account can access the following outlets, outlet groups and serial ports:
outlet A1 which has a descriptive name of DataServer_1, outlet A2 which has a descriptive name of WebServer_1,
group ServerGroup_1 group ServerGroup_2 and Console serial port.
Technical Specifications
Authentication START Packet includes:
action = 1 (TAC_PLUS_AUTHEN_LOGIN)
priv_lvl = 0 (TAC_PLUS_PRIV_LVL_MIN)
authen_type = 1 (TAC_PLUS_AUTHEN_TYPE_ASCII)
service = 1 (TAC_PLUS_AUTHEN_SVC_LOGIN)
user = (entered username)
port = (access path into the unit)
rem_addr = ‘Sentry3_xxxxxx’ (xxxxxx is last six digits of MAC address)
data = ‘‘ (null)
NOTE:
The password is sent in a “continue” packet.
Authorization REQUEST Packet includes:
authen_method = 6 (TAC_PLUS_AUTHEN_METH_TACACSPLUS)
priv_lvl = 0 (TAC_PLUS_PRIV_LVL_MIN)
authen_type = 1 (TAC_PLUS_AUTHEN_TYPE_ASCII)
authen_service = 1 (TAC_PLUS_AUTHEN_SVC_LOGIN)
user = (entered username)
port = (access path into the unit)
rem_addr = ‘Sentry3_
xxxxxx
’ (xxxxxx is last six digits of Ethernet MAC address)
service = ‘shell’ (for exec)
cmd = ‘‘ (null)
NOTE:
The access paths into the PDU which support are Console, Telnet, SSH, HTTP, and HTTPS. For Console and
Modem, an administrator is allowed to rename these ports, in which case the assigned name is used.