Configuring the LED display orientation:
The Set Option Display command configures the LED display orientation.
To configure the LED display orientation:
At the Switched CDU: prompt, type
set option display
, followed by
normal, inverted
, or
auto
, and press
Enter
.
Example
The following sets the LED display orientation to Inverted:
Switched CDU: set option display inverted<Enter>
NOTES:
Only specific PDU models are equipped with an accelerometer chip that senses device orientation. If equipped, your PDU automatically
aligns the LED display orientation depending on its current direction, and “Auto” will display in the Show Options command by default.
In addition, the actual mounting of the unit, such as such as “<Normal> or <Inverted>”, appears to the right of the "Auto" option when
you issue the Show Options command. However, even if your model does have the sensor for device orientation, you can still
issue the Set Option Display command with either the Normal or Inverted option to override the capability of the hardware.
If your model does not have the accelerometer chip, you will need to configure the LED display orientation by entering the Normal
or Inverted option.
Enabling or disabling strong passwords:
The Set Option Strong Password command is used to enable or disable the requirements for strong passwords. When
enabled, all new passwords must be a minimum of 8 characters in length with at least one uppercase letter, one
lowercase letter, one number and one special character.
To enable or disable strong passwords:
At the Switched CDU: prompt, type
set option strong password
, followed by
enabled
or
disabled
and press
Enter
.
Enabling or disabling the external configuration reset button:
The Set Option Button command enables or disables the external configuration reset button. This feature can enhance
system security by protecting the PDU configurations from being reset locally.
NOTE:
If this feature has been enabled and the administrative account username/password has been lost, then the PDU must be returned to
the factory for non-warranty reset of the configuration.
To enable or disable the configuration reset button:
At the Switched CDU: prompt, type
set option button
, followed by
enabled
or
disabled
and press
Enter
.
Enabling or disabling the ‘more’ prompt:
The Set Option More command enables or disables the ‘more’ prompt for display of data larger than the terminal
window.
To enable or disable ‘more’:
At the Switched CDU: prompt, type
set option more
, followed by
enabled
or
disabled
and press
Enter
.
Setting the outlet sequence order:
The PDU allows the configuration of power-on sequence for outlets.
The Normal option powers-on outlets in ascending numeric order by outlet number, for example, from outlet 1-8. The
Reversed option powers on outlets in descending order by outlet number; for example, from outlet 8-1.
The Reversed option is useful when the PDU is mounted with inverted orientation and the last outlet (in this example,
outlet 8) is in the first position.
At the Switched CDU: prompt, type
set option outletsequence
, followed by
normal
or
reversed
, and press
Enter
.
Setting the temperature scale:
The Set Option TempScale command sets the temperature scale reported by the PDU.
To set the temperature scale:
At the Switched CDU: prompt, type
set option tempscale
, followed by
celsius
or
fahrenheit
and press
Enter
.