Switched PDU
Installation and Operations Manual
Advanced Operations
113
Enabling or disabling a change trap:
The Set Trap Outlet Change command is used to enable or disable an Outlet Change trap.
To Enable or Disable a Change trap:
At the Switched CDU: prompt, type
set trap outlet change
, followed by the outlet name and
on
or
off
.
Press
Enter
, or
Type
set trap outlet
change all
, followed by
on
or
off
and press
Enter
.
Example
The following command enables the Change trap for the third outlet on the first infeed of the second tower, using the
outlet’s absolute name:
Switched CDU: set trap outlet change .ba3 on<Enter>
Enabling or disabling the temp trap:
The Set Trap THS Temp command is used to enable or disable the Temp trap.
To Enable or Disable the Temp trap:
At the Switched CDU: prompt, type
set trap ths temp
, followed by the sensor name and
on
or
off
. Press
Enter
.
Example
The following command enables the Temp trap for the first temperature-humidity sensor:
Switched CDU: set trap ths temp .a1 on<Enter>
Setting the temperature sensor threshold limits:
The Set Trap THS Templow and Set Trap THS Temphigh commands are used to set the lower and upper threshold
limits for the Temperature sensor.
To set the Temperature threshold limits:
At the Switched CDU: prompt, type
set trap ths
,
templow
or
temphigh
, followed by the sensor name and a value
from 0 to 123 in degrees Celsius. Press
Enter
.
Example
The following command sets the second temperature high threshold limit to 95:
Switched CDU: set trap ths temphigh .a2 95<Enter>
Configuring temperature recovery delta (hysteresis):
The Temperature Recovery Delta command allows configuration of the number of degrees of change needed to
recover from a temperature alarm.
To configure the temperature recovery delta:
At the Switched CDU: prompt, type
set trap ths tempdelta
, followed by the sensor name, the number of degrees for
the recovery delta, and press
Enter
.
Valid range is 0-30 C or 0-54 F.
Example
The following command configures the recovery delta at 2 degrees Fahrenheit for temperature/humidity sensor .A1:
Switched CDU: set trap ths tempdelta temp_humid_sensor_A1 2<Enter>