Installation Switched PDU
Installation and Operations Manual
Attaching Safety Earth Ground Connection
Server Technology PDUs are supplied with an external safety ground connection to provide an alternate ground path for fault
currents, and to maintain the same ground reference between it and the equipment rack.
NOTE:
The auxiliary external ground location may vary. Most PDUs will have it located near the power cord entry located near the
symbol.
User-supplied materials:
One 5 mm internal (or external) tooth star washer;
One 4.0 mm
2
(10 AWG) wire with 5 mm ring terminal;
One metric M5 x 6 mm coarse pitch screw.
Instructions:
1.
Connect one end of the ground wire to the equipment cabinet or local ground.
2.
Locate the PDU external ground near the
symbol.
3.
Connect the other end with a ring terminal and a M5 screw to the PDU external ground. To ensure proper grounding
to the chassis, use a star washer between the ring terminal and the PDU.