www.weg.net
Manual of Electric Motors
89
E
N
G
LI
S
H
The alarm temperature limits and thermal protection shutdowns can be defined according to the application;
however these temperature limits can not exceed the values in Table 6.4.
Table 6.4
- Maximum activation temperature of the thermal protections
Component
Insulation class
Maximum temperature of the protection setting (°C)
Alarm
Tripping
Winding
B
-
130
F
130
155
H
155
180
Bearing
All
110
120
Notes
:
1) The number and type of the installed protection devices are stated on the accessory nameplate of the motor.
2) If the motor is supplied with calibrated resistance, (for example, Pt-100), the motor protection system must be set according to the
operating temperatures indicated in Table 6.4.
6.11. RESISTANCE TEMPERATURE DETECTORS (PT-100)
The thermocouples Pt-100 are made of materials, whose resistance depends on the temperature variation,
intrinsic property of some materials (usually platinum, nickel or copper), calibrated resistance. Its operation is
based on the principle that the electric resistance of a metallic conductor varies linearly with the temperature,
thus allowing a continuous monitoring of the motor warm-up through the controller display ensuring a high level
of precision and answer stability. These devices are widely used for measuring temperatures in various industry
sectors.
In general these devices are used in installations where precise temperature control is required, for example, in
installation for irregular or intermittent duty.
The same detector may be used for alarm and tripping purposes.
Table 6.5 and Figure 6.16 show the equivalence between the Pt-100 resistance and the temperature.
Page 160
Содержание BN 5-12 Series
Страница 13: ...TAB 1 DEVICE DATA SHEETS ...
Страница 18: ...TAB 2 APPROVED SUBMITTAL ...
Страница 23: ...All data subject to change without notice 1 800 ASK 4WEG www weg net 14 ...
Страница 26: ...Your advantages our pumps ...
Страница 45: ...ADV 2 13E And what can we get flowing for you Your nearest contact Or visit www seepex com ...
Страница 117: ...TAB 3 INSTALLATION OPERATIONS AND MAINTENANCE ...
Страница 133: ...Page 37 ...
Страница 233: ...www weg net Manual of Electric Motors 64 ENGLISH Figure 2 1 IEC motor nameplate Page 135 ...
Страница 234: ...www weg net Manual of Electric Motors 65 ENGLISH Figure 2 2 NEMA motor nameplate Page 136 ...
Страница 306: ...TAB 4 AS BUILTS AND SUPPLEMENTAL INFORMATION ...
Страница 307: ...R Page 29 ...
Страница 308: ...R Page 30 ...