8 ACU-220
SATEL
– input in normal state – output turned off.
wireless 230 V AC controllers – controls the relay (230 V AC power supply):
– input activated – relay turned on (power on),
– input in normal state – relay turned off (power off).
For each wireless device registered to the controller, indicate the control input. For some
devices (ASP-200 and ASP-215 sirens, ACX-210 and ACX-220 expanders, ASW-210
controller), which take up two or more positions on the list of devices, the control input must
be indicated for each position. One input can control any number of devices.
You can program the control inputs as NO (normally open) or NC (normally closed).
To the control inputs, you can connect e.g. outputs of the control panel or another device.
3.5 Programmable outputs [universal module of wireless devices]
8 OC type outputs (OUT1…OUT8) can indicate the status of wireless devices, or can be
controlled with keyfobs. Depending on the type of wireless device, the output is turned on
when:
alarm occurs (wireless detector),
signaling is triggered (wireless siren),
230 V AC mains is lost (ARU-200 radio signal repeater),
battery trouble occurs (ARU-200 radio signal repeater),
expander input is activated (expander of wired zones/outputs),
ASW-200 or ASW-210 controller relay is turned on / ASW-200 controller button is pressed
/ ASW-210 controller input is activated.
Each wireless device must be assigned to an output. If the device occupies two or more
positions on the device list, each position must be assigned to an output. You can assign any
number of devices to one output.
Each keyfob button can control one output.
You can program the outputs as NO (normally open) or NC (normally closed).
The outputs can be connected, for example, to the control panel zones, or they can be used
to control operation of automation devices.
4
Installation of the controller
Disconnect power before making any electrical connections.
Be careful during installation to avoid damage to the components located on the
controller electronics board.
4.1 Selecting a mounting location
The controller should be installed indoors, in spaces with normal air humidity. Prior to
installation you should plan the arrangement of all ABAX 2 wireless devices which are to be
operated by the controller. Select the installation place so that these devices are located
within the controller operating range. Remember that thick walls, metal partitions, etc. will
reduce the range of the radio signal. It is recommended that the controller be mounted high
above the floor. This will allow you to get a better range of radio communication and avoid
the risk of the controller being accidentally covered by people moving around the premises.
Installing the device in close vicinity of electrical systems is not recommended, since it can
adversely affect the range of radio signal.