9.9.6.2 Commissioning
After entering the plant data correctly, you will have to check if the encoder systems of the VVVF
controller and the controller correspond to one another.
To to this, please move several metres
in the same direction
several
times
, in insepection or recovery mode, and check the calculated pulley
diameter of the VVVF controller in the display menu. This value should
correspond to the parameterized value as much as possible.
If not, please adjust the suggested pulley diameter in the menu
Setup –
Plant data.
9.9.6.3 DCP4 Setup options
When DCP04 mode is activated, the corresponding setup menu is
enabled.
Here, you can set up the stopping behaviour.
Note: Setting
StopmitV0 = 1
delivers the better travel experience because the acceleration
disappears in the brief constant phase which allows the mechanics to settle even before stopping.
Setting
DCP04
----------------------
○
StopmitV0 = 1
Direct landing with short creep track
StopmitV0 = 0
Direct landing time optimized
Setting
General Settings
----------------------
○
General Setings
pull.diam. 562 mm
----------------------
○
Anzeigen
DCP-Data
----------------------
○
DCP-Data
Treib.(Calc)
562 mm
----------------------
○
FRC
Setting
----------------------
○
DCP04
StopmitV0 0
----------------------
○
Содержание FRC-F Series
Страница 1: ...9 581 140 6 Page 1 VVVF Controller for Elevators FRC Q FRC F IMD...
Страница 16: ...9 581 140 6 Page 16...
Страница 17: ...9 581 140 6 Page 17...
Страница 23: ...9 581 140 6 Page 23...
Страница 85: ...9 581 140 6 Page 85...
Страница 90: ...9 581 140 6 Page 90...
Страница 122: ...9 581 140 6 Page 122...
Страница 123: ...9 581 140 6 Page 123...
Страница 124: ...9 581 140 6 Page 124...
Страница 125: ...9 581 140 6 Page 125...