Now check the stopping accuracy using the elevator control. To do this, drive to each floor from both
directions.
If the drive always runs too short or too far, you can still adjust the direct landing:
Press buttons "E" and "C" simultaneously for 3 seconds to activate the service menu
Choose menu Setting - CANopen.
The CANopen menu contains a parameter for correcting the braking
distance. The default value is 100%
If the drive don’t reach the level-position (stops too early):
Increase the parameter value by 5%.
If the drive overrides the level-position (stops too late):
Decrease the parameter value by 5%.
Now check again the stopping accuracy and refine or repeat the correction.
Since the inverter operates internally with a resolution of 1mm, a deviation of ± 1mm
Is quite normal and does not require any further correction.
Setting
CANopen
----------------------
○
CANopen
braking adj 105%
----------------------
○
CANopen
braking adj 100%
----------------------
○
CANopen
braking adj 95%-
---------------------
○