9.7.6 Special functions
9.7.6.1 Loosening cabin from safety catch
If you enter 1 for the travel speed V1, a set value jump will be prescribed.
As a result, a jerk-like torque will be built up and the cabin can be
loosened from the safety catch more easily. Additionally, the maximum
VVVF controller current is output. This function must be activated again
after each attempted start, i.e. the value for V1MaxRuck is reset to 0 after
each attempted start.
9.7.6.2 Automatic measurement of motor characteristic
Enter 1 to activate a motor characteristic measurement. This enables an
optimum torque utilization of the machine. Please carry out this
measurement only after consulting RST-Elektronik.
9.7.6.3 Automatic test of motor connection upon the start of drive
If you enter a 1, the connection to the motor is checked upon each start
of a drive. In this way, wiring defects or open contactors are detected
immediately.
9.7.6.4 Determination of angle offset in synchronous machines
See
Section 9.10.2
.
Special functions
Einph.On 1
----------------------
Special functions
V1MaxRuck 0
----------------------
Special functions
Tuning 0
----------------------
Special functions
Motor test 1
----------------------