Electrical installation
Connecting the relay outputs
Relay output 1 (limit value alarm)
Terminal 11/10/9 - White, Brown, Green
Relay output 1 is energised when a limit value is exceeded and switches the connection from
COM to NO. An indicator light or horn can be connected to relay output 1 to signal a limit
violation.
If the limit value is exceeded, relay output 1 remains switched in the position (connection from
COM to NO) until the measured water hardness is below the limit value again. Afterwards, the
limit value transgression is cancelled again and relay output 1 switches back (connection from
COM to NC).
1 12
11
10 9
8
6
5
4
2
1
1 12 11 10 9
8
6
5
4
2
1
Illustration 11: Electrical installation relay output 1 (junction box)