Electrical installation
When working on the electrical connections, the following instructions must be observed:
•
Screwable and plug-in terminal blocks are suitable for accommodating rigid single-core
conductors up to 2.5 mm². Fine-core conductors up to 1.5 mm² can be connected with
wire end ferrules, with plastic collars or up to 2.5 mm² without plastic collars. To loosen a
terminal, use a slotted screwdriver SL with a maximum blade width of 3 mm.
•
The relevant VDE regulations must be observed during all installation work.
Before opening the housing, disconnect the unit from the power supply and secure
it against unintentional reconnection.
The installation of a suitable electrical disconnecting device is the responsibility of
the system operator.
The maximum connected load of all loads must not exceed 250 VAC / 2.5 A or
100 VDC / 2.5 A. Provide suitable interference suppression for inductive loads.
Work on the electrical equipment of the system/machine may only be carried
out by a trained electrician!
Voltage
Voltage
Voltage