98 • Start Up, Leak Check Mode
Gas Tracer Operator’s Manual, CSA Version
The alarm LED’s and buzzer will pulse several times. After this, press
and release the RESET SILENCE button to continue.
•
If the unit is due for calibration and CL EXPRD is set to NOT USE, then
the following screen displays.
The Gas Tracer cannot be used until a calibration has been performed
either by selecting AUTO CAL, ONE CAL, or PPM CAL in the
Maintenance Mode menu. See “Calibrating Using Auto Calibration” on
page 115, “Calibrating Using Single Calibration” on page 118, or
“Calibrating and Bump Testing the PPM Combustible Sensor” on
page 125 for calibration instructions.
•
If calibration is not due or CL EXPRD is set to NO EFFECT, then the
following screen appears for a few seconds indicating when the next
calibration is due.
7. If BP RMNDR is turned on (factory setting is OFF), the screen that appears
next depends on how BP EXPRD is set in the Maintenance Mode Menu
(page 148).
•
If the unit is due for a bump test and BP EXPRD is set to CONFIRM
(factory setting), then the following screen displays.
The alarm LED’s and buzzer will pulse several times. After this, press the
RESET SILENCE button until you hear a beep to continue.
FAIL
C--LIMIT
2011
9
30
69d
NEXT CAL
tESt
B--LIMIT