6. Alarm Activation
6-1 Gas alarm activation
93 / 168
6-1-3 Contact operation (self-latching)
If self-latching is set, the contacts will activate when the gas concentration reaches or exceeds the alarm
setpoint.
The contact operation is automatically reset when the gas concentration falls below the alarm setpoint after
resetting.
The alarm lamps flash when an alarm occurs. The lamps stop flashing and remains constantly lit when reset.
Then, the lamps go out when the gas concentration falls below the alarm setpoint.
NOTE
To cancel an alarm, press the MENU/ESC key, SET key, ▲ key, or ▼ key in detection mode.
<Alarm pattern (H-HH)>
Normal
Alarm
Reset
Gas concentration
■
ALM1 alarm lamp (red)
■
ALM2 alarm lamp (red)
■
ALM1 alarm contact
■
ALM2 alarm contact
■
ALM1 alarm lamp (red)
■
ALM2 alarm lamp (red)
■
ALM1 alarm contact
■
ALM2 alarm contact
■
ALM1 alarm lamp (red)
■
ALM2 alarm lamp (red)
■
ALM1 alarm contact
■
ALM2 alarm contact
■
ALM1 alarm lamp (red)
■
ALM2 alarm lamp (red)
■
ALM1 alarm contact
■
ALM2 alarm contact
Reset
Reset
Reset
Reset
Reset
Содержание GD-3EC
Страница 28: ...2 Important Safety Information 2 4 Safety information 28 168 Connection examples GD 3RI GD 3ECB SD 3SC SD 3SC...
Страница 169: ...11 Appendix Revision History 169 168...
Страница 170: ...11 Appendix Revision History 170 168...
Страница 171: ...11 Appendix Revision History 171 168...
Страница 172: ...11 Appendix Revision History 172 168...
Страница 173: ...11 Appendix Revision History 173 168...
Страница 174: ...11 Appendix Revision History 174 168...
Страница 175: ...11 Appendix Revision History 175 168...
Страница 176: ...11 Appendix Revision History 176 168...
Страница 177: ...11 Appendix Revision History 177 168...