background image

Microprocessor control
Wall mounted
16 zone protection (across 1 or 2 zones)
4 - 20mA signal input
Relay outputs (incl. fire alarm interface)
Positive safety feature
Measuring range 0 - 20% LEL/0 - 300ppm
IP65 protective rating
EN50194 for explosive gases
EN50291 for toxic gases
3 year guarantee

Application

Duomo is recognised within the gas industry for
providing a comprehensive range of low cost, high
reliability gas detection for many applications. We have
installed and commissioned natural gas and carbon
monoxide sensors in applications such as boiler rooms,
kitchens, car parks, aircraft hangers, factories and
shopping centres. The BX216 is the command centre for
the complete range of Duomo gas sensors. All Duomo
products are manufactured to meet relevant European
Normatives and proposals for explosive and toxic gases.

Features

The BX216 is a wall mounted microprocessor based gas
detector control unit. It can be configured to meet
customer requirements. The following parameters can
be changed using the on board menu:

Number of sensors from 1 to 16
Type of gas to be sensed (explosive or toxic)
Pre-alarm level for each sensor

The number of zones (1 or 2)

Main alarm relay action (latching or auto-reset)
Positive safety feature
Alarm logging function
Event history

The BX216 has five main terminal blocks for the
following;

The incoming mains supply
The alarm circuit wiring (including fault, siren,

pre-alarm and main alarm relays)

The power supply to the sensors
The 4 - 20mA return cable from the sensors

A 0 - 10V output to BMS proportional to the 4 - 20mA

return signal

The front panel has an LCD display showing the date,
time, current sensor levels and much more. LED's on the
panel indicate what alarm status the unit is in, as well as
any faults present on the connected sensors.

Operation

The BX216 can detect both explosive and toxic gases.
When the remote sensor detects the presence of the
target gas a 4 - 20mA signal is sent to the detector,
proportional to the level of gas. The BX216 then
operates a pre-alarm relay - used for remote sirens or
visual indicators. If the level of gas continues to rise then
the second pre-alarm is actuated. In the case of
explosive gases, when the gas reaches a preset level, the
main alarm relay is activated to break the electrical
supply to the gas safety shut-off valve (SSOV). The BX216
also has a separate volt-free sensor fault relay that
actuates if the correct return signal is not sensed by the
detector. There is also the provision of a fire alarm
interface. This controller can be interlinked with a fire
alarm so that in the event of a fire, it would shut down
the gas supply.

BX

3

16

 

Gas

 

Detector

w:

www.duomo.co.uk

-

e:

[email protected]

-

t:

01905 797989

-

f:

01905 774296

|

©

Duomo (UK) Ltd. 2007

Summary of Contents for BX216

Page 1: ...story The BX216 has five main terminal blocks for the following The incoming mains supply The alarm circuit wiring including fault siren pre alarm and main alarm relays The power supply to the sensors The 4 20mA return cable from the sensors A 0 10V output to BMS proportional to the 4 20mA return signal The front panel has an LCD display showing the date time current sensor levels and much more LE...

Page 2: ...mming menus 12 Printer Port Allows a printer to be attached to print off all the data stored in memory 13 Test Button This button simulates a gas leak and tests the full funcionality of the BX216 14 Reset Button When pressed it resets all internal memory 15 Output Terminal Block Converts the 4 20mA return signal from the sensors to a 0 10V output connection for BMS 16 Sensor Return Terminal Block ...

Page 3: ... ZONE 2 NC NC NO NO C NC NO C NC NO C C 3 5A Power Supply 230V 14 13 NC NO C NC NO C Relay outputs 2 1 3 12 11 10 9 8 7 6 5 4 FAULT RELAY SIREN RELAY PRE ALARM ZONE 1 MAIN ALARM ZONE 1 MAIN ALARM ZONE 2 PRE ALARM ZONE 2 NC NC NO NO C NC NO C NC NO C C 3 5A Power Supply 230V 14 13 NC NO C NC NO C Relay outputs 2 1 3 12 11 10 9 8 7 6 5 4 FAULT RELAY SIREN RELAY PRE ALARM ZONE 1 MAIN ALARM ZONE 1 MAI...

Page 4: ...ne is displayed for 8 seconds in turn To cycle through the zones use the left and right keys on the keypad To pause on a zone press the Enter key Press the Enter again to move on and continue cycling through The sensors must be mounted as shown below with the sintered head pointing vertically down When replacing sensors never seperate a sensing head from its PCB The sensor will have been calibrate...

Page 5: ...s 1234567812345678 Zone 1 Zone 2 TExxxxxx 12345678 xxxxxxxx 12345678 T been set to detect toxic gas i e carbon monoxide An means it has been set to detect explosive gas i e methane Once you have set each zone up move down to the and press Enter This will move you into the next screen that allows you to set the pre alarm level for each sensor Note If no sensor is attached to a particular zone you w...

Page 6: ...eters for each option are as follows Controls how the main alarm relay operates in an alarm condition Continuous means the relay will remain activated after the alarm has passed Impulse means the relay will activate for 20 seconds and then revert back to its normal state Moving the cursor down to the and pressing Enter will move you down to the next screen shown below To go back to the top menu pr...

Page 7: ...nsor Blackout Power to the BX216 has been lost Check incoming 230V power supply Reset The BX216 has been reset using the button on the fascia following an alarm condition Low Battery The backup battery not supplied is running low Probe Enabled The sensor indicated has been enabled using the internal setup Prove Disabled The sensor indicated has been disabled using the internal setup Hard Reset The...

Page 8: ...onfigured this will remain on until the RESET button is pressed 5 In order to conduct a full function test it is essential to use Duomo or equivalent calibrated test gas The maximum concentrations are 40 LEL for methane in air 350ppm for carbon monoxide 0 85 MOL for propane Any higher than this can reduce sensor life NOTE NEVER TEST USING NEAT GAS THIS WILL POISON THE SENSOR 6 To simulate a sensor...

Page 9: ...orrect Check that the sensor wiring is correctly terminated at both the sensor and detector Check that 12V DC is present at the sensor The green light on the sensor should be illuminated Pressing the TEST button it is possible to check the efficiency of the device and if the sensors have been connected correctly Check that the connections are correct and that power is supplied to the valve i e the...

Page 10: ...ation No of remote sensors 16 No of selectable zones 2 Monitored gas indication Through illuminated display Input signal 4 20mA Device precision 1 FS Reaction time 2 seconds Working temperature 10 C to 45 C Start up self diagnostic delay 90 seconds Suitable for use with sensor type SGM595 CO100Ar CO200A SG895 Maximum distance for sensor connection 100m Cable diameter for sensors 1mm2 CSA Dimemsion...

Reviews: