7. Maintenance
7-3 Performing tests (test mode)
115 / 168
7-3-3 Performing fault test
Test to check whether an alarm is triggered when a fault occurs in the product.
WARNING
Depending on the settings, contact and gas concentration outputs may be activated during fault testing,
even in maintenance mode. Take care during fault testing.
1 Press the ▲ or ▼ key in maintenance mode several times
to select [2-0], then press the SET key.
2 Press the ▲ or ▼ key to select [2-0.2], then press the SET
key.
3 Press the ▲ or ▼ key to select [on], then press the SET
key.
4 Check to confirm that a fault alarm is triggered.
The fault lamp (FAULT) lights up (yellow) when a fault alarm is
triggered.
5 Once the fault test is complete, press the ▲ or ▼ key to
select [oFF], then press the SET key.
The fault alarm is cleared. The fault lamp (FAULT) goes out.
Fault alarms can also be cleared by pressing the MENU/ESC key.
Fault lamp
(FAULT)
Содержание GD-3EC
Страница 28: ...2 Important Safety Information 2 4 Safety information 28 168 Connection examples GD 3RI GD 3ECB SD 3SC SD 3SC...
Страница 169: ...11 Appendix Revision History 169 168...
Страница 170: ...11 Appendix Revision History 170 168...
Страница 171: ...11 Appendix Revision History 171 168...
Страница 172: ...11 Appendix Revision History 172 168...
Страница 173: ...11 Appendix Revision History 173 168...
Страница 174: ...11 Appendix Revision History 174 168...
Страница 175: ...11 Appendix Revision History 175 168...
Страница 176: ...11 Appendix Revision History 176 168...
Страница 177: ...11 Appendix Revision History 177 168...