4. Installation
4-1 Installation precautions
44 / 168
CAUTION
A de-energized b contact (break contact) may result in momentary opening in the event of an external
force or other physical impact. If a b contact is used as an alarm contact, implement measures to account
for such momentary operations—for example, by adding a delay operation (of approximately one
second) to the signal on the b contact receiving side.