RFL 9785
RFL Electronics Inc.
June 18, 2009
18-3
(973) 334-3100
Output Over Current Protection:
+5.00Vdc
1.0 Amp foldback to 50% Max Load Current (500mA)
+/- 15Vdc
Internal regulator @ 1.8 Amp foldback/Thermal
+12 Vdc
Internal regulator @ 1.8 Amp foldback/Thermal
Output Ripple Voltage:
Measured differentially with full load @ 150Vdc input
+5.00Vdc
<200
mv
pp
+15.0 Vdc
<1200 mv pp
-15.0 Vdc
<1200 mv pp
+12.0Vdc
<1200
mv
pp
Input Overvoltage Protection:
184 Vdc minimum (38 Vdc to 150 Vdc supply)
388 Vdc minimum (200 Vdc to 300 Vdc supply)
Isolation:
As specified in ANSI/IEEE C37.90
3000Vdc
Input
to
Output
3000Vdc
Input
to
Chassis
Surge Withstand Requirements:
As specified in ANSI/IEEE C37.90.1
The Power Supply input passes Oscillatory and Fast Transient SWC tests with no impact on
power supply outputs.
Environmental Specifications:
Temp
Range -20
o
C to +60
o
C Still Air
Humidity
95%
@
40
o
C
Indicators:
DS1 – Normal
Green