Define the voltage / current mode for analog inputs before setting the torque
reference.
●
Parameter C3.41 'Torque reference channel' is used to set torque reference
channel.
●
Parameters C3.42 'Torque reference minimum value' and C3.43 'Torque refer-
ence maximum value' are used to define the curve characteristic for the tor-
que reference.
Fig. 12-68: Torque reference characteristic curve
Step 3: Set the direction of torque reference
Code
Name
Setting range
Default
Min.
Attri.
E0.01 First run command source
0: Panel
1: Multi-function digital input
2: Communication
0
–
Stop
Example 1:
[E0.01] = '0: Panel'
[C3.41] = '0: AI1 analog input'
[C3.42] = 0.0 %
[C3.43] = 100.0 %
EFC x610 Series
Bosch Rexroth AG
Functions and Parameters
DOK-RCON03-EFC-X610***-IT05-EN-P