Torque boost setting
The torque boost function is used to obtain higher output torque and better sta-
bilization by boosting the output voltage, especially at low speed.
Code
Name
Setting range
Default
Min.
Attri.
C2.21 Torque boost setting
0.0 %: Automatic boost
0.1... 20.0 %: Manual boost
0.0
0.1
Run
C2.22 Automatic torque boost factor 0...320 %
50
1
Run
C2.00 V/f curve mode
0: Linear
1: Square
2: User-defined
0
–
Stop
C1.08 Motor rated frequency
5.00...400.00 Hz
50.00
0.01
Stop
●
Manual torque boost with linear or user-defined V/f curve
In this V/f curve, the output voltage starts to be boosted when the output fre-
quency is lower than half of [C1.08].
Example: If [C1.08] = 50.00 Hz, then torque boost function is active when out-
put frequency is lower than 25.00 Hz.
Fig. 12-64: Manual torque boost with linear or user-defined V/f curve
[C2.21] is the voltage boost value at 0.00 Hz. The actual voltage boost values for
other frequency points decreases in linear along with output frequency increase.
●
Manual torque boost with square curve
In this square V/f curve, the output voltage starts to be boosted when the out-
put frequency is lower than [C1.08].
Example: If [C1.08] = 50.00 Hz, then torque boost function is active when the
output frequency is lower than 50.00 Hz.
Bosch Rexroth AG
Functions and Parameters
EFC x610 Series
220/389
DOK-RCON03-EFC-X610***-IT05-EN-P
Содержание EFC 3610 Series
Страница 18: ...Bosch Rexroth AG EFC x610 Series XVI DOK RCON03 EFC X610 IT05 EN P ...
Страница 332: ...Fig 15 15 0020 N 03_0025 N 03 Bosch Rexroth AG Accessories EFC x610 Series 300 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 333: ...Fig 15 16 0025 A 05 EFC x610 Series Bosch Rexroth AG Accessories DOK RCON03 EFC X610 IT05 EN P 301 389 ...
Страница 336: ...Fig 15 21 0250 N 05 Bosch Rexroth AG Accessories EFC x610 Series 304 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 421: ...Notes EFC x610 Series Bosch Rexroth AG ...