Fault status register (0x7FB0)
The fault status of frequency converter can be monitored by reading the regis-
ter.This register is read-only. The definition of each bit is shown in the table be-
low:
bit
Value
Description
Errors
15
1
Miscellaneous
ESS-, UH, Pdr, t-Er, AdE-, AibE,
EPS-, dir1, dir2, FFE-, E.Par, PbrE,
APP-, APE1, APE2, APE3, APE4,
APE5, etc.
0
OK
14...10
Reserved
9
1
Internal fault
idE-, idP-, idA-, OCd-
0
OK
8
1
Communication fault
rS-, Fdi-, OCc
0
OK
7
1
External fault
E-St
0
OK
6
1
Fan fault
FF
0
OK
5
1
Under voltage
UE-1
0
OK
4
1
Phase loss
IPH.L, OPH.L
0
OK
3
1
Overheat
OH, Ot
0
OK
2
1
Overload
OL-1, OL-2
0
OK
1
1
Over voltage
OE-1, OE-2, OE-3, OE-4
0
OK
0
1
Over current
OC-1, OC-2, OC-3, SC
0
OK
Tab. 14-27: Fault status register (0x7FB0)
Communication frequency setting register (0x7F01)
The address of frequency setting register for communication control is 0x7F01.
This register is for read and write. When 'First frequency setting source' [E0.00]
= '20: Communication', the frequency converter can be set with writing data to
this address.
EFC x610 Series
Bosch Rexroth AG
Communication
DOK-RCON03-EFC-X610***-IT05-EN-P
271/389
Содержание EFC 3610 Series
Страница 18: ...Bosch Rexroth AG EFC x610 Series XVI DOK RCON03 EFC X610 IT05 EN P ...
Страница 332: ...Fig 15 15 0020 N 03_0025 N 03 Bosch Rexroth AG Accessories EFC x610 Series 300 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 333: ...Fig 15 16 0025 A 05 EFC x610 Series Bosch Rexroth AG Accessories DOK RCON03 EFC X610 IT05 EN P 301 389 ...
Страница 336: ...Fig 15 21 0250 N 05 Bosch Rexroth AG Accessories EFC x610 Series 304 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 421: ...Notes EFC x610 Series Bosch Rexroth AG ...