13.4.30 Error 45 (E.Par): Parameter Settings Invalid
Possible reason
Solution
Parameter settings are invalid after firmware update or ex-
tension card removed or parameter copy
1. Check parameter group '-EP-' and
modify the parameter values ap-
peared in '-EP-'
2. Initialize all parameters
13.4.31 Error 46 (U.Par): Unknown Parameter Restore Error
Possible reason
Solution
If one or more parameters in the backup were not found in
the device, they will be skipped during parameter restore
Check the differences between the dif-
ferent firmware versions
13.4.32 Error 48 (idA-): Internal Communication Error
Possible reason
Solution
Internal error caused by communication between control
boards
Contact with service
13.4.33 Error 49 (idP-): Internal Parameter Error
Possible reason
Solution
Internal error caused by parameter handling
Contact with service
13.4.34 Error 50 (idE-): Converter Internal Error
Possible reason
Solution
Internal error occurs
Contact with service
13.4.35 Error 51 (OCd-): Extension Card Internal Error
Possible reason
Solution
Extension card was successfully detected by the device at
startup, but the communication failed afterwards
Contact with service
13.4.36 Error 52 (OCc): Extension Card PDOs Configuration Error
Possible reason
Solution
Internal communication error between communication card
and converter control board
Contact with service
EFC x610 Series
Bosch Rexroth AG
Diagnosis
DOK-RCON03-EFC-X610***-IT05-EN-P
249/389
Содержание EFC 3610 Series
Страница 18: ...Bosch Rexroth AG EFC x610 Series XVI DOK RCON03 EFC X610 IT05 EN P ...
Страница 332: ...Fig 15 15 0020 N 03_0025 N 03 Bosch Rexroth AG Accessories EFC x610 Series 300 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 333: ...Fig 15 16 0025 A 05 EFC x610 Series Bosch Rexroth AG Accessories DOK RCON03 EFC X610 IT05 EN P 301 389 ...
Страница 336: ...Fig 15 21 0250 N 05 Bosch Rexroth AG Accessories EFC x610 Series 304 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 421: ...Notes EFC x610 Series Bosch Rexroth AG ...