12.2.6 I/O Card Terminal Configuration
Set digital input terminals
Code
Name
Setting range
Default Min.
Attri.
H8.00 EX1 input
0...46
0
–
Stop
H8.01 EX2 input
0
–
Stop
H8.02 EX3 input
0
–
Stop
H8.03 EX4 input
0
–
Stop
Setting range of H8.00...H8.03:
0: No function assigned
1: Multi-speed control input 1
2: Multi-speed control input 2
3: Multi-speed control input 3
4: Multi-speed control input 4
10: Acceleration/deceleration time 1 activation
11: Acceleration/deceleration time 2 activation
12: Acceleration/deceleration time 3 activation
15: Freewheeling stop activation
16: Stop DC-braking activation
20: Frequency Up command
21: Frequency Down command
22: Up / Down command reset
23: Torque / Speed control switch
25: 3-wire control
26: Simple PLC stop
27: Simple PLC pause
30: Second frequency setting source activation
31: Second run command source activation
32: Fault signal N.O. contact input
33: Fault signal N.C. contact input
34: Error reset
35: Forward running (FWD)
36: Reverse running (REV)
37: Forward jog
38: Reverse jog
39: Counter input
EFC x610 Series
Bosch Rexroth AG
Functions and Parameters
DOK-RCON03-EFC-X610***-IT05-EN-P
115/389
Содержание EFC 3610 Series
Страница 18: ...Bosch Rexroth AG EFC x610 Series XVI DOK RCON03 EFC X610 IT05 EN P ...
Страница 332: ...Fig 15 15 0020 N 03_0025 N 03 Bosch Rexroth AG Accessories EFC x610 Series 300 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 333: ...Fig 15 16 0025 A 05 EFC x610 Series Bosch Rexroth AG Accessories DOK RCON03 EFC X610 IT05 EN P 301 389 ...
Страница 336: ...Fig 15 21 0250 N 05 Bosch Rexroth AG Accessories EFC x610 Series 304 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 421: ...Notes EFC x610 Series Bosch Rexroth AG ...