12.5.2 Run Command Source
First and second run command source configuration
Code
Name
Setting range
Default
Min.
Attri.
E0.01 First run command source
0...2
0
–
Stop
E0.03 Second run command source
0...2
1
–
Stop
●
0: Operating panel
Control the frequency converter for run and stop with <Run>, <Stop> buttons
on the operating panel.
Control the running direction by setting parameters U0.00 'Direction control
by panel' and E0.17 'Direction control'.
●
1: Multi-function digital input
Control the frequency converter for run, stop and running direction by setting
digital inputs.
●
2: Communication
Control the frequency converter for run, stop and running direction with Mod-
bus communication protocol.
Switch between first and second run command source
Code
Name
Setting range
Default
Min.
Attri.
E1.00 X1 input
31: Second run command source activation
35
–
Stop
E1.01 X2 input
36
–
Stop
E1.02 X3 input
0
–
Stop
E1.03 X4 input
0
–
Stop
E1.04 X5 input
0
–
Stop
H8.00 EX1 input
0
–
Stop
H8.01 EX2 input
0
–
Stop
H8.02 EX3 input
0
–
Stop
H8.03 EX4 input
0
–
Stop
If status of the selected terminal is changed when converter is running, the run
command source will be switched and the converter will freewheel to stop. The
active / inactive of digital input is triggered by voltage level.
Bosch Rexroth AG
Functions and Parameters
EFC x610 Series
150/389
DOK-RCON03-EFC-X610***-IT05-EN-P
Содержание EFC 3610 Series
Страница 18: ...Bosch Rexroth AG EFC x610 Series XVI DOK RCON03 EFC X610 IT05 EN P ...
Страница 332: ...Fig 15 15 0020 N 03_0025 N 03 Bosch Rexroth AG Accessories EFC x610 Series 300 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 333: ...Fig 15 16 0025 A 05 EFC x610 Series Bosch Rexroth AG Accessories DOK RCON03 EFC X610 IT05 EN P 301 389 ...
Страница 336: ...Fig 15 21 0250 N 05 Bosch Rexroth AG Accessories EFC x610 Series 304 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 421: ...Notes EFC x610 Series Bosch Rexroth AG ...