Minimum immunity requirements for PDSs intended for use in the second envi-
ronment
Port
Phenomenon
Basic standard
for test
method
Level
Performance
(acceptance
criterion)
Enclosur
e por
t
ESD
IEC 61000-4-2
4 kV CD or 8 kV AD
if CD impossible
B
Radio-frequency electromag-
netic field, amplitude modula-
ted
IEC 61000-4-3
80...1000 MHz 10 V/m
1.4....0 GHz 3 V/m
2.0...2.7 GHz 1 V/m
80 % AM (1 kHz)
A
Po
w
er por
ts
Fast transient-burst
IEC 61000-4-4 2 kV/5 kHz
B
Surge 1.2/50 μs, 8/20 μs
IEC 61000-4-5 1 kV
a
, 2 kV
b
B
Conducted radio-frequency
common mode
IEC 61000-4-6
0.15...80 MHz 10 V
80 % AM (1 kHz)
A
Po
w
er
int
er
faces
Fast transient-burst
IEC 61000-4-4
2 kV/5 kHz
Capacitive clamp
B
Signal int
er
faces
Fast transient-burst
IEC 61000-4-4
1 kV/5 kHz
Capacitive clamp
B
Conducted radio-frequency
common mode
IEC 61000-4-6
0.15...80 MHz 10 V
80 % AM (1 kHz)
A
Por
ts of pr
oces
s
measur
ement
contr
ol lines
Fast transient-burst
IEC 61000-4-4
2 kV/5 kHz
Capacitive clamp
B
Conducted radio-frequency
common mode
IEC 61000-4-6
0.15...80 MHz 10 V
80 % AM (1 kHz)
A
Tab. 9-1: Minimum immunity requirements for PDSs intended for use in the second environ-
ment
Bosch Rexroth AG
Electromagnetic Compatibility (EMC)
EFC x610 Series
64/389
DOK-RCON03-EFC-X610***-IT05-EN-P
Содержание EFC 3610 Series
Страница 18: ...Bosch Rexroth AG EFC x610 Series XVI DOK RCON03 EFC X610 IT05 EN P ...
Страница 332: ...Fig 15 15 0020 N 03_0025 N 03 Bosch Rexroth AG Accessories EFC x610 Series 300 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 333: ...Fig 15 16 0025 A 05 EFC x610 Series Bosch Rexroth AG Accessories DOK RCON03 EFC X610 IT05 EN P 301 389 ...
Страница 336: ...Fig 15 21 0250 N 05 Bosch Rexroth AG Accessories EFC x610 Series 304 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 421: ...Notes EFC x610 Series Bosch Rexroth AG ...