19.3.3 Group C: Power Parameters
C0: Power control parameters
Code
Name
Setting range
Default
Min.
Attri.
Control mode
(EFC 5610 only)
0: V/f control
1: Sensorless vector con-
trol
0
–
Stop
Normal / Heavy duty setting
①
0: ND (Normal duty)
1: HD (Heavy duty)
1
–
Stop
Carrier frequency
DOM
DOM
1
Run
Carrier frequency
automatic adjustment
0: Inactive
1: Active
1
–
Stop
Brake chopper start voltage
②
1P 200 VAC: 300...390 V
385
1
Stop
3P 400 VAC: 600...785 V
770
Brake chopper duty cycle
②
1...100 %
100
1
Stop
Overvoltage prevention mode
0...3
3
–
Stop
Stall overvoltage
prevention level
1P 200 VAC: 300...390 V
385
1
Stop
3P 400 VAC: 600...785 V
770
Stall overcurrent
prevention level
③
20.0 %...[C2.42]
150.0
0.1
Stop
Phase loss protection mode
0...3
3
–
Run
Converter overload
pre-warning level
20.0...200.0 %
110.0
0.1
Stop
Converter overload
pre-warning delay
0.0...20.0 s
2.0
0.1
Stop
Power loss ride-through mode
0: Inactive
1: Output disable
2: Regain kinetic energy
3: Regain kinetic energy,
decelerate to stop
0
–
Stop
C0.41 Recovery delay
0.10...30.00 s
0.50
0.01
Stop
C0.42 Power loss ride-through action
voltage
1P 200 VAC: 216...366 V
240
1
Stop
3P 400 VAC: 406...739 V
440
C0.43 Power loss ride-through recover
voltage
1P 200 VAC: 223...373 V
250
1
Stop
3P 400 VAC: 413...746 V
450
C0.44 Decelerating to stop time
0.1...6,000.0 s
5.0
0.1
Stop
EFC x610 Series
Bosch Rexroth AG
Appendix
DOK-RCON03-EFC-X610***-IT05-EN-P
333/389
Содержание EFC 3610 Series
Страница 18: ...Bosch Rexroth AG EFC x610 Series XVI DOK RCON03 EFC X610 IT05 EN P ...
Страница 332: ...Fig 15 15 0020 N 03_0025 N 03 Bosch Rexroth AG Accessories EFC x610 Series 300 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 333: ...Fig 15 16 0025 A 05 EFC x610 Series Bosch Rexroth AG Accessories DOK RCON03 EFC X610 IT05 EN P 301 389 ...
Страница 336: ...Fig 15 21 0250 N 05 Bosch Rexroth AG Accessories EFC x610 Series 304 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 421: ...Notes EFC x610 Series Bosch Rexroth AG ...