Set digital / analog output terminals
Code
Name
Setting range
Default Min.
Attri.
H8.20 EDO output setting
0...20
1
–
Stop
H8.21 Extended relay output
selection
1
–
Stop
H8.25 EAO output mode
0: 0…10 V; 1: 0...20 mA
0
–
Run
H8.26 EAO output selection
0: Running frequency
1: Set frequency
2: Output current
4: Output voltage
5: Output power
6: AI1 analog input
7: AI2 analog input
8: EAI analog input
11: Motor temperature sensor power
0
–
Run
H8.27 EAO gain
0.00...10.00
1.00
0.01
Run
Perform the self-test function
Code
Name
Setting range
Default Min.
Attri.
H8.87 I/O card output channel
diagnosis
0: Inactive
1: EAO diagnosis
2: EDO diagnosis
3: ERO diagnosis
4: All output diagnosis
0
–
Stop
●
0: Inactive
The test is complete. All outputs are restored to default settings.
●
1: EAO diagnosis. The analog output of I/O card outputs 10 V.
●
2: EDO diagnosis. The open collector output of I/O card outputs 10 V.
●
3: ERO diagnosis. The relay output of I/O card is closed.
●
4: All output diagnosis. EAO, ERO, EDO are all tested with the above methods.
Bosch Rexroth AG
Functions and Parameters
EFC x610 Series
120/389
DOK-RCON03-EFC-X610***-IT05-EN-P
Содержание EFC 3610 Series
Страница 18: ...Bosch Rexroth AG EFC x610 Series XVI DOK RCON03 EFC X610 IT05 EN P ...
Страница 332: ...Fig 15 15 0020 N 03_0025 N 03 Bosch Rexroth AG Accessories EFC x610 Series 300 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 333: ...Fig 15 16 0025 A 05 EFC x610 Series Bosch Rexroth AG Accessories DOK RCON03 EFC X610 IT05 EN P 301 389 ...
Страница 336: ...Fig 15 21 0250 N 05 Bosch Rexroth AG Accessories EFC x610 Series 304 389 DOK RCON03 EFC X610 IT05 EN P ...
Страница 421: ...Notes EFC x610 Series Bosch Rexroth AG ...