9.2 Group B - OUTPUT AND REGULATION
16
c.out
Command Output (Word modbus 2016)
Command output type selection
0
Command Q1; Alarm 1 Q2; Alarm 2 AO (0..20 mA). (
Default
)
1
Command Q1; Alarm 1 Q2; Alarm 2 AO (4..20 mA).
2
Valve command: Q1 (open) - Q2 (close); Alarm 1 AO (0..20 mA)
3
Valve command: Q1 (open) - Q2 (close); Alarm 1 AO (4..20 mA)
4
Command AO (0...20 mA); Alarm 1 Q1; Allarme 2 Q2.
5
Command AO (4...20 mA); Alarm 1 Q1; Allarme 2 Q2.
Comando
Allarme 1
Allarme 2
0
Q1
Q2
AO (0..20 mA)
1
Q1
Q2
AO (4..20 mA)
2
Q1(open),Q2(close)
AO (0..20 mA)
-
3
Q1(open),Q2(close)
AO (4..20 mA)
-
4
AO (0..20 mA)
Q1
Q2
5
AO (4..20 mA)
Q1
Q2
17
init.S.
Initial State (Word modbus 2017)
Selects controller status at starting.
0
Start (
Default
)
1 Stop
2
Stored. Backs the controller to the Start/Stop status existing before
the switching-off.
18
Act.t.
Action type (Word modbus 2018)
0
Heating (N.O.) (
Default
)
1
Cooling (N.C.)
19
c. HY.
Command Hysteresis (Word modbus 2019)
Hysteresis in ON/OFF
-10000..+10000 [digit] (degrees.tenths for temperature sensors).
Default
2.
20
c. S.e.
Command State Error (Word modbus 2020)
State of contact for command output in case of error.
0
0 mA if command on AO. Open contact if command on Q1. Open
valve if valve command. (
Default)
1
4 mA if command on AO. Closed contact if command on Q1. Closed
valve if valve command.
2
20 mA if command on AO. Open contact if command on Q1. Open
valve if valve command.
3
21.5 mA if command on AO. Closed contact if command on Q1.
Closed valve if valve command.