20 -
User manual
Modbus
address
Descrizione
Read
Write
Reset
value
1015
Current CT OFF (ampere with tenth)
RO
0
1016
Key status (0=rilasciato, 1=premuto)
RO
0
1017
Dip 1 value
RO
0
1100
Process (if temperature, no tenth)
RO
-
1101
Command setpoint (if temperature, no tenth)
R/W
EEPROM
1102
Alarm 1 setpoint (if temperature, no tenth)
R/W
EEPROM
1103
Command output percentage (0-1000)
Heating output percentage in double loop
R/W
0
1104
Heating output percentage (0-100)
Heating output percentage in double loop
R/W
0
1105
Cooling output percentage in double loop
(0-1000)
RO
0
1106
Cooling output percentage in double loop (0-100) RO
0
1107
Output status (0=off, 1=on)
Bit 0 = OUT1
Bit 1 = OUT2
RO
0
1108
Command output percentage (0-10000)
Heating output percentage in doulbe loop
R/W
0
1200
Process (if temperature, with tenth)
RO
?
1201
Command setpoint (if temperature, with tenth)
R/W
EEPROM
1202
Alarm 1 setpoint (if temperature, with tenth)
R/W
EEPROM
1203
Alarm 2 setpoint (if temperature, with tenth)
R/W
EEPROM
1204
Start/Stop
0=controller in STOP
1=controller in START
R/W
0
1205
With automatic tuning (word 2005 = 1):
0=autotuning function OFF
1=autotuning in progress
RO
0
With manual tuning (word 2005 = 2):
0=autotuning function OFF
1=autotuning ON
R/W
0
With synchronized tuning (word 2005 = 3):
0=autotuning function OFF
1=command out. OFF (forces the cooling)
2=command out. ON (forces the heating)
3=autotuning ON
4=autotuning completed
R/W
0
1206
Automatic/manual selection
0=automatic ; 1=manual
R/W
0
1207
Real value (gradient) command setpoint (if
temperature, with tenth)
R
-