26 -
User manual
21
c. S.s.
Command State Stop (Word modbus 2021)
State of contact for command output with controller in STOP
0
0 mA if command on AO. Open contact if command on Q1. Open
valve if valve command. (
Default)
1
4 mA if command on AO. Closed contact if command on Q1. Closed
valve if valve command.
2
20 mA if command on AO. Open contact if command on Q1. Open
valve if valve command.
3
21.5 mA if command on AO. Closed contact if command on Q1.
Closed valve if valve command.
22
c. re.
Command Reset (Word modbus 2022)
Type of reset for state of command contact (always automatic in P.I.D.
functioning)
0
Automatic reset (
Default
)
1
Manual reset (by word 1029)
2
Manual reset stored (keeps relay status also after an eventual power
failure)
23
c. de.
Command Delay (Word modbus 2023)
Command delay (only in ON / OFF functioning).
-3600..+3600 seconds.
Default
: 0.
Negative: delay in switching off phase.
Positive: delay in activation phase.
24
vAL.t.
Valve Time (Word modbus 2024)
Valve time.
1...300 seconds.
Default
: 60.
25
au.ma.
Automatic / Manual (Word modbus 2025)
Enable automatic / manual selection.
0
Disabled (
Default
)
1 Enabled
2
Enabled with memory
26÷30
Reserved Parameters - Group B
Reserved parameters - Group B