36 -
User manual
9.9 GROUP I - SERIALE
111
sL.ad.
Slave Address (Word modbus 2111)
Selects slave address for serial communication when all DIP 1 contacts are set
on OFF
1...254.
Default
: 247.
112
bd.rt.
Baud Rate (Word modbus 2112)
Selects slave address for serial communication when all DIP 2 contacts are set
on OFF
0
4800 bit/s
1
9600 bit/s
2
19200 bit/s (
Default
)
3
28800 bit/s
4
38400 bit/s
5
57600 bit/s
6
115200 bit/s
113
s.p.p.
Serial Port Parameters (Word modbus 2113)
Selects the type of format for the modbus RTU communication
0
8-N-1
8 bit, no parity, 1 stop bit (
Default
)
1
8-E-1
8 bit, even parity, 1 stop bit
2
8-O-1
8 bit, odd parity, 1 stop bit
3
8-N-2
8 bit, no parity, 2 stop bit
4
8-E-2
8 bit, even parity, 2 stop bit
5
8-O-2
8 bit, odd parity, 2 stop bit
114
se.de.
Serial Delay (Word modbus 2114)
Selects the serial delay.
0...100 ms.
Default
: 0 ms.
115
off.L.
Off Line (Word modbus 2115)
Selects the off-line time. If no communication is available within the selected
time, the controller will switch-off the command output.
0
Offline disabled (
Default
)
1...6000 tenths of seconds (Es. 100 = 10.0 s)
116÷120
Reserved Parameters - Group I
Reserved parameters - Group I