Alarm 1 Reset (Word modbus 2061)
Alarm 1 contact reset type.
0
Automatic reset (
Default
)
1
Manual reset (by word 1210)
2
Manual reset stored. (keeps relay status also after an eventual
power failure)
62
a.1.de.
Alarm 1 Delay (Word modbus 2062)
Alarm 1 Delay. -3600..+3600 seconds.
Default
: 0.
Negative: delay in alarm output phase.
Positive: delay in alarm entry phase.
63÷67
Reserved Parameters - Group D
Reserved parameters - Group D
9.5 GROUP E - ALARM 2
68
AL.2
Alarm 2 (Word modbus 2068)
The alarm intervention is related to Alarm 2.
0
Disabled (
Default
)
1
Absolute alarm (threshold) referred to process active above
2
Absolute alarm (threshold) referred to process active below
3
Band alarm
4
Upper deviation alarm
5
Lower deviation alarm
6
Absolute alarm referred to active setpoint above
7
Absolute alarm referred to active setpoint below
8
Status alarm (active in RUN / START)
9
Cold actuator auxiliary (Cold action in double loop)
10
Heater Break Alarm and Overcurrent Alarm
11
Sensor error. Active alarm in case of broken sensor
12
Remote. Alarm enabled by word 1212