22 -
User manual
Modbus
address
Descrizione
Read
Write
Reset
value
1220
Command output percentage (0-100)
Heating output percentage in double loop
R/W
0
1221
Cooling output percentage in double loop (0-100) RO
0
1222
Current CT (ampere with tenth)
RO
0
1223
Current media CT (ampere with tenth)
RO
0
1224
Current CT ON (ampere with tenth)
RO
0
1225
Current CT OFF (ampere with tenth)
RO
0
1226
Cold junction temperature (degree with tenth)
RO
-
1227
Output status (0=off, 1=on)
Bit 0 = OUT1
Bit 1 = OUT2
RO
0
1228
Led status (0 = OFF, 1 = ON)
Bit0 = Green led
Bit1 = Red led OUT1
Bit2 = Red led OUT2
RO
0
1229
Key status (0=rilasciato, 1=premuto)
RO
0
1230
Dip 1 value
RO
0
1231
Dip 2 value
RO
0
1232
Process (if temperature, no tenth)
RO
-
1233
Command setpoint (if temperature, no tenth)
R/W
EEPROM
1234
Alarm 1 Setpoint (if temperature, no tenth)
R/W
EEPROM
1235
Alarm 2 Setpoint (if temperature, no tenth)
R/W
EEPROM
1300
Latch on setting
R/W
0
1301
Latch on lower limit calibration
R/W
0
1302
Latch on upper limit calibration
R/W
0
1303
Latch on virtual zero calibration
R/W
0
1500
Process (if temperature, with tenth)
RO
?
1501
CT instantaneous current (ampere with tenth)
RO
0
1502
Current CT ON (ampere with tenth)
RO
0
1503
Current CT OFF (ampere with tenth)
RO
0
1504
Key status (0=rilasciato, 1=premuto)
RO
0
1505
Dip 1 value
RO
0
1506
Dip 2 value
RO
0
1507
Digital output status (0=off, 1=on)
Bit 0 = OUT1
Bit 1 = OUT2
R/W
0
1508
Analogue output value
R/W
0
2001
Parameter 1
R/W
EEPROM
2002
Parameter 2
R/W
EEPROM
...
Parameter ...
R/W
EEPROM
2143
Parameter 143
R/W
EEPROM
Содержание ISO-plus-CAN