28 -
User manual
38
o.o.s.
Off Over Setpoint (Word modbus 2038)
In P.I.D. functioning enables the command outoput switching off, when
passing a specific threshold (se Par.37).
0
Disabled. (
Default
)
1 Enabled
39
of.d.t.
Off Deviation Threshold (Word modbus 2039)
Selects command setpoint deviation to calculate the intervention threshold of
“Off Over Setpoint”
function.
-10000...+10000 [digit] (degrees.tenths for temperature sensors) (
Default
: 0)
40
c.t.
Cycle Time (Word modbus 2040)
Cycle time (for PID on teleruptor 15s ; for PID on SSR 2s.)
1-300 seconds (
Default
:15s)
41
coo.F
Cooling Fluid (Word modbus 2041)
Type of refrigerant fluid for heating / cooling PID.
Enable cooling output on par. AL.1 or AL.2.
0
Air. (
Default
)
1 Oil
2 Water
42
P.b.M.
Proportional Band Multiplier (Word modbus 2042)
Proportional band for cooling action is done by the value of par. 30 multiplied
for this value.
100(1.00)...500(5.00).
Default
: 100(1.00)
43
ov.d.b.
Overlap / Dead Band (Word modbus 2043)
Dead band combination for heating / cooling P.I.D.
-200(-20.0%)...500(50.0%)
Negative: dead band.
Positive: overlapping.
Default
: 0(0.0%)
44
co.c.t.
Cooling Cycle Time (Word modbus 2044)
Cycle time for cooling output.
1-300 seconds (
Default
:10s)
45
L.L.o.P.
Lower Limit Output Percentage (Word modbus 2045)
Selects min. value for command output percentage.
0%...100%,
Default
: 0%.