- 35
9.8 GROUP H - RETRANSMISSION
100
retr.
Retransmission (Word modbus 2100)
Retransmission for output 0/4..20 mA. Parameters 98 and 99 define upper/
lower limit of operating sequence
0
Disabled (
Default
)
1 Process
2
Command setpoint
3
Alarm 1 setpoint
4
Alarm 2 setpoint
5
Ampere from current transformer
6
Remote value retransmission (word 1213)
101
re.ty.
Retransmission Type (Word modbus 2101)
Select the type of Retransmission
0
0...20 mA
1
4...20 mA (
Default
)
102
Lo.L.r.
Lower Limit Retransmission (Word modbus 2102)
Linear output lower limit range (value related to 0/4 mA)
-32767..+32767 [digit] (degrees for temperature sensors),
Default
: 0.
103
up.L.r.
Upper Limit Retransmission (Word modbus 2103)
Linear output upper limit range (value related to 20 mA)
-32767..+32767 [digit] (degrees for temperature sensors),
Default
: 10000.
104
re.s.e.
Retransmission State Error (Word modbus 2104)
Selects the value of the analogue output in Volt in case of error
0
0 mA (
Default
)
1
4 mA
2
20 mA
3
21.5 mA
105
re.s.S.
Retransmission State Stop (Word modbus 2105)
Defines the analogue output value with controller in STOP
0
0 mA (
Default
)
1
4 mA
2
20 mA
3
21.5 mA
4
Retransmission active in STOP
106÷110
Reserved Parameters - Group H
Reserved parameters - Group H