9.6 GROUP F - SOFT-START
80
SS.TY.
Soft-Start Type (Word modbus 2080)
Enables and selects soft-start type
0
Disabled (
Default
)
1 Gradient
2 Percentage
81
SS.Gr.
Soft-Start gradient (Word modbus 2081)
Rise / fall gradient for soft-start.
1..10000 Digit/hour (tenths of degree/hour if temperature). (
Default
: 1000)
82
SS.Pe.
Soft-Start Percentage (Word modbus 2082)
Value of the output percentage during Soft-start.
0..100%. (
Default
: 50%)
83
SS.tH.
Soft-Start Threshold (Word modbus 2083)
Threshold under which the device enables percentage soft-start function, at
starting.
-10000...10000 [digit] (degrees.tenths for temperature sensors) (
Default
: 1000)
84
SS.ti.
Soft-Start Time (Word modbus 2084)
Max. softstart duration: if the process doesn’t reach the threshold entered on
parameter 50 within the selected time, the controller will start to regulate on
setpoint value.
0 Disabled
1...1440 minutes. (
Default
: 15 minutes)
85÷89
Reserved Parameters - Group F
Reserved parameters - Group F