User manual
- 23
9
Table of configuration parameters
9.1 GROUP A - ANALOGUE INPUT
1
SEN.
Sensor (Word modbus 2001)
Analogue input configuration / sensor selection
0
Tc-K
-260 °C..1360 °C. (
Default
)
1
Tc-S
-40 °C..1760 °C
2
Tc-R
-40 °C..1760 °C
3
Tc-J
-200 °C..1200 °C
4
Tc-T
-260 °C..400 °C
5
Tc-E
-260 °C..980 °C
6
Tc-N
-260 °C..1280 °C
7
Tc-B
100 °C..1820 °C
8
Pt100
-100 °C..600 °C
9
Ni100
-60 °C..180 °C
10
NTC10K
-40 °C..125 °C
11
PTC1K
-50 °C..150 °C
12
Pt500
-100 °C..600 °C
13
Pt1000
-100 °C..600 °C
14
0..10 V
15
0..20 mA
16
4..20 mA
17
0..60 mV
18
Potenziometer (set the value on parameter 5)
2
deGr.
Degree (Word modbus 2002)
0
°C
Centigrade (
Default
)
1 °F
Fahrenheit
2 K
Kelvin
3
Lo.L.i.
Lower Linear Input (Word modbus 2003)
Range AN1 lower limit only for linear input. Ex: with input 4..20 mA this
parameter takes value associated to 4 mA.
-32767..+32767
,
Default
: 0.
4
up.L.i.
Upper Linear Input (Word modbus 2004)
Range AN1 upper limit only for linear input. Ex: with input 4..20 mA this
parameter takes value associated to 20 mA.
-32767..+32767
.
Default
:10000
5
Pot.v.
Potentiometer Value (Word modbus 2005)
Select potentiometer value
1..150 kohm
.
Default
: 10kohm
Содержание ISO-plus-CAN