User manual -
19
Modbus
address
Descrizione
Read
Write
Reset
value
1004
With automatic tuning (word 2005 = 1):
0=autotuning function OFF
1=autotuning in progress
RO
0
With manual tuning (word 2005 = 2):
0=autotuning function OFF
1=autotuning ON
R/W
0
With synchronized tuning (word 2005 = 3):
0=autotuning function OFF
1=command out. OFF (forces the cooling)
2=command out. ON (forces the heating)
3=autotuning ON
4=autotuning completed
R/W
0
1005
Automatic/manual selection
0=automatic ; 1=manual
R/W
0
1006
Output status (0=off, 1=on)
Bit 0 = OUT1
Bit 1 = OUT2
RO
0
1007
Led status (0 = OFF, 1 = ON)
Bit0 = Green led
Bit1 = Red led OUT1
Bit2 = Red led OUT2
RO
0
1008
Alarm status (0=absent, 1=present)
Bit0 = Allarme 1
Bit1 = Allarme 2
RO
0
1009
Error flags
Bit0 = Cold junction error
Bit1 = Process error (sensor)
Bit2 = Error in eeprom writing
Bit3 = Error in eeprom reading
Bit4 = Error missing calibration
Bit5 = Generic error
Bit6 = Hardware error
Bit7 = Error H.B.A. (SSR in short circuit)
Bit8 = Error H.B.A. (SSR/open charge)
Bit9 = Error H.B.A. (partial break of the charge)
Bit10= Overcurrent error
RO
0
1010
Cold junction temperature (degree with tenth)
RO
-
1011
Command output percentage (0-10000)
Heating output percentage in double loop
R/W
0
1012
Cooling output percentage in double loop
(0-10000)
RO
0
1013
Current CT (ampere with tenth)
RO
0
1014
Current CT ON (ampere with tenth)
RO
0