User manual -
21
Modbus
address
Descrizione
Read
Write
Reset
value
1208
Alarm status (0=absent, 1=present)
Bit0 = Allarme 1
Bit1 = Allarme 2
RO
0
1209
Command output manual reset: write 0 to reset
command output.
In reading 0=can not be reset, 1=can be reset
R/W
0
1210
Alarms manual reset: write 0 to reset all alarms.
In reading 0=can not be reset, 1=can be reset
Bit0 = Allarme 1
Bit1 = Allarme 2
R/W
0
1211
Remote alarm 1 state (0=absent, 1=present)
R/W
0
1212
Remote alarm 2 state (0=absent, 1=present)
R/W
0
1213
AO value by serial (Par.100 = 6)
R/W
0
1214
Error flags 1
Bit0 = Cold junction error
Bit1 = Process error (sensor)
Bit2 = Error in eeprom writing
Bit3 = Error in eeprom reading
Bit4 = Error missing calibration
Bit5 = Generic error
Bit6 = Hardware error
Bit7 = Error H.B.A. (SSR in short circuit)
Bit8 = Error H.B.A. (SSR/open charge)
Bit9 = Error H.B.A. (partial break of the charge)
Bit10= Overcurrent error
RO
0
1215
Error flags 2
Bit0 = Error eeprom calibrations
Bit1 = Error eeprom calibration constants
Bit2 = Error eeprom parameters
Bit3 = Error eeprom setpoint
Bit4 = Error eeprom service datas A
Bit5 = Error eeprom service datas B
Bit6 = Error eeprom service datas C
RO
0
1216
Command output percentage (0-10000)
Heating output percentage in double loop
R/W
0
1217
Cooling output percentage in double loop
(0-10000)
RO
0
1218
Command output percentage (0-1000)
Heating output percentage in double loop
R/W
0
1219
Cooling output percentage in double loop
(0-1000)
RO
0