User manual
5.1 Wiring diagram
ISO-plus-RS4
5.1.a
Power Supply
1
+
–
24 VDC
2
Power supply 24 VDC ±15% – 3 VA
5.1.b
Analogue Input
+
–
AI
TC
Shield / Schermo
13
14
For thermocouples K, S, R, J, T, E, N, B.
• Comply with polarity
• For possible extensions, use compensated cable
and terminals suitable for the thermocouples
used(compensated)
• When shielded cable is used, it should be grounded at
one side only
AI
Rosso
Red
Bianco
White
Rosso
Red
Shield / Schermo
PT/NI100
13
14
15
For thermoresistances PT100, Ni100.
• For the three-wire connection use wires with the same
section
• For the two-wire connection short-circuit terminals 13
and 15
• When shielded cable is used, it should be grounded at
one side only
AI
Shield / Schermo
PT
C/NT
C
14
15
For thermoresistances NTC, PTC, PT500, PT1000 and
linear potentiometers
When shielded cable is used, it should be grounded at one
side only to avoid ground loop currents
+
–
AI V
mA
Shield / Schermo
13
14
For linear signals in Volt and mA
Comply with polarity
When shielded cable is used, it should be grounded at one
side only to avoid ground loop currents